installation
vacon • 29
24-hour support: +358-(0)40-
8371 150 • Email: [email protected]
5
5.2
Fan cooling
5.2.1
Frames FI9 to FI14
Enough free space must be left around the inverter to ensure sufficient air circulation and cooling.
You will find the required dimensions for free space in the table below.
If several units are mounted on top of each other, the required free space equals 2 * C (see figure
below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the air
intake of the upper unit. When planning the cooling for the space, take into consideration that the
inverter’s heat loss is approx. 2.5% of the nominal capacity.
Type
Dimensions [mm]
A
B
B
2
C
NXI_0168 – 0300 5
NXI_0125 – 0208 6
200
20
Min. 300
NXI_0385 – 0520 5
NXI_0261 – 0416 6
200
20
Min. 300
NXI_0590 – 1030 5
NXI_0460 – 0820 6
200
20
0
Min. 300
NXI_1150 – 1450 5
NXI_0920 – 1180 6
200
20
0
Min. 300
NXI_1770 – 2700 5
NXI_1500 – 2250 6
The dimensions as per FI13
module
Table 5-1. Mounting space dimensions
Figure 5-7. Installation space.
A = free space above the inverter
B = distance between inverter and cabinet wall
B
2
= distance between two inverters
C = free space underneath of the inverter