4.4.2
BASIC PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.1)
Table 25: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.1.1
Min frequency
0.00
P2.1.2
Hz
0.00
101
P2.1.2
Max frequency
P2.1.1
320.00
Hz
50.00
102
If f
max
> than the
motor synchro-
nous speed,
check suitability
for motor and
drive system.
P2.1.3
Acceleration
time 1
0.1
3000.0
s
0.0
103
Gives the time that
is necessary for
the output fre-
quency to increase
from zero fre-
quency to maxi-
mum frequency.
P2.1.4
Decelaration
time 1
0.1
3000.0
s
0.0
104
Gives the time that
is necessary for
the output fre-
quency to
decrease from
maximum fre-
quency to zero fre-
quency.
P2.1.5
Current limit
0.1 x I
H
2 x I
H
A
I
L
107
P2.1.6 *
Nominal voltage
of the motor
180
690
V
NX2:
230V
NX5:
400V
NX6:
690V
110
Find the value Un
on the rating plate
of the motor. Find
out if the motor
connection is Delta
or Star.
P2.1.7 *
Nominal fre-
quency of the
motor
8.00
320.00
Hz
50.00
111
Find the value fn
on the rating plate
of the motor.
P2.1.8 *
Nominal speed of
the motor
24
20 000
rpm
1440
112
Find the value nn
on the rating plate
of the motor.
P2.1.9 *
Nominal current
of the motor
0.1 x I
H
2 X I
H
A
I
H
113
Find the value In
on the rating plate
of the motor.
VACON · 74
MULTI-STEP SPEED CONTROL APPLICATION
4
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......