3.4.3
INPUT SIGNALS (CONTROL KEYPAD: MENU M2 -> G2.2)
Table 16: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.1 *** Place A Start/Stop
logic selection
0
8
0
300
Logic = 0
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Start
reverse
Logic = 1
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Run
enable
Logic = 3
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Stop
pulse
Logic = 4
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Motor
potentiometer UP
Logic = 5
Ctrl sgn 1 = Start
forward (edge)
Ctrl sgn 2 = Start
reverse (edge)
Logic = 6
Ctrl sgn 1 = Start
(edge) / Stop
Ctrl sgn 2 = Reverse
Logic = 7
Ctrl sgn 1 = Start
(edge) / Stop
Ctrl sgn 2 = Run
enable
LOCAL/REMOTE CONTROL APPLICATION
VACON · 49
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
3
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......