Arfiff05 Standard AFE-II
vacon •
65
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7.9
ID Functions
Here you will find the functions that use the parameter ID number to control and monitor the signal.
7.9.1
Value Control
The value control parameters are used to control an input signal parameter.
P2.9.1.1
Control Input Signal ID ID1580
With this parameter you can select which signal is used to control the selected
parameter.
P2.9.1.2
Control Off Limit
ID1581
This parameter defines the limit when the selected parameter value is forced to Off
value.
P2.9.1.3
Control On Limit
ID1582
This parameter defines the limit when the selected parameter value is forced to O n
value.
P2.9.1.4
Control Off Value
ID1583
This parameter defines the value that is used when the used input signal is below Off
limit.
P2.9.1.5
Control On Value
ID1584
This parameter defines the value that is used when the used input signal is above On
limit.
P2.9.1.6
Control Output Signal ID
ID1585
This parameter defines which parameter is forced to On and Off values when selected
input signal exceeds the set limits.
P2.9.1.7
Control Mode
ID1586
This parameter defines how the value control output behaves.
0 = SR ABS
Absolute input value is used to make a step change in the output between On and Off
values.
Off
value
On
value
Control
Off
value
Control
On
Value
Off
value
On
value
Negative
Positive
Figure 1.
1 = Scale ABS
Absolute input value is scaled linearly between On and Off values.