CANopen option board interface
vacon • 65
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8
8.
CAN
OPEN
OPTION
BOARD
INTERFACE
By default, the CANopen option board is configured to operate in Drive Profile mode. The drive pro-
file implementation is ‘Velocity Mode’ which is defined in CiA 402 specification with PDO set for the
AC drive. The board can also be configured into Manufacturer specific mode.
8.1
Supported drive modes
Drive modes can be selected by writing the desired mode in Modes of Operation (0x6060) object or
by selecting the mode from panel. The active mode of operation can be read from object Modes of
Operation Display (0x6061).
The supported drive modes object will return value 0x80000002, which is described in table below.
Table 60. Supported drive modes
Bit(s)
Description
31
Manufacturer specific Bypass
mode
30-2
Not supported
1
Velocity mode
0
Not supported
Table 61. Drive modes
Value
Mode name
Description
2
Velocity mode
The CiA 402 Drive Profile mode where the control
of the drive is done using a control word and
speed reference value as specified in the drive
profile specification.
-1
Bypass mode
In this mode, the Drive control can be done using
raw process data which is exchanged with drive
application. The drive profile state machine and
the related objects become invalid.
-3
Puller mode
CiA 420 EUROMAP profiles. Restricted availabil-
ity, requires use of special application.
-4
Co-Extruder
mode
Table 62. Operating mode related objects
Index
Description
0x6060
Modes of Operation
0x6061
Modes of Operation Display
0x6502
Supported Drive Modes