CANopen protocol description
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.7.3
0X1003 - Pre-defined Error Field
Pre-defined error field is a list of errors signaled with an EMCY object, listing the error history of
up to 9 error entries. Sub-index 1 contains the latest error.
3.7.4
0X1005 - COB ID SYNC
Defines the synchronisation message COB ID. Receiving the sync message causes actions in the
PDOs that have a synchronous transmission mode.
3.7.5
0X100C - Guard Time
The object contains the guard time in milliseconds. As a default, guarding is disabled.
3.7.6
0X100D - Life Time Factor
Life time factor is used together with guard time, which is multiplied with the life time factor.
Node life time = life time factor x guard time. If node life time is zero, guarding is disabled.
Table 35: 0x1003 Pre-defined error field
Index
Sub-index
Value
Name
Data type
Access
0x1003
0
0x0
Number of
errors
UNSIGNED8
ro
1
0x0
Standard error
field
UNSIGNED32
ro
..
..
..
..
..
9
0x0
Standard error
field
UNSIGNED32
ro
Table 36: 0x1005 COB ID sync
Index
Sub-index
Value
Name
Data type
Access
0x1005
-
0x00000080
COB ID sync
UNSIGNED32
r/w
Table 37: 0x100C Guard time
Index
Sub-index
Value
Name
Data type
Access
0x100C
-
0x0000
Guard time
UNSIGNED16
r/w
Table 38: 0x100D Guard time
Index
Sub-index
Value
Name
Data type
Access
0x100D
-
0x00
Guard time
UNSIGNED8
r/w