7.14 ID Functions
Listed here are the functions that use the parameter ID number to control and monitor the signal.
7.14.1
Value Control
The value control parameters are used to control an input signal parameter.
P2.14.1.1 Control Input Signal ID ID1580
“ContrInSignal ID”
With this parameter you can select what signal is used to control selected parameter.
P2.14.1.2 Control Off Limit
ID1581
“Contrl Off Limit”
This parameter defines the limit when the selected parameter value is forced to Off
value.
P2.14.1.3 Control On Limit
ID1582
“Contrl On Limit”
This parameter defines the limit when the selected parameter value is forced to On
value.
P2.14.1.4 Control Off Value
ID1583
“Contrl Off Value”
This parameter defines the value that is used when the used input signal is below Off
limit.
P2.14.1.5 Control On Value
ID1584
“Contrl On Value”
This parameter defines the value that is used when the used input signal is above On
limit.
P2.14.1.6 Control Output Signal ID
ID1585
“ContrlOutSignID”
This parameter defines which parameter is forced to On and Off values when selected
input signal exceeds the set limits.
P2.14.1.7 Control Mode
ID1586
“Control Mode”
This parameter defines how the value control output behaves.
0 =
SR ABS
Absolute input value is used to make a step change in the output between On and Off
values.
Off
value
On
value
Control
Off
value
Control
On
Value
Off
value
On
value
Negative
Positive