7.4 Input signals
7.4.1 Basic Settings
P2.4.1.1
Start/Stop logic selection
ID300
“Start/Stop Logic”
This parameter defines the start stop logic when using the I/O control. Some of these
selections do not include
the ’R
everse
’
command. The Reverse command can be
activated by a
separate digital input “Reverse”.
0
“Forw –
Rev” –
Forward Start
–
Reverse Start
Start 1: closed contact = start forward
DI “Start 1”
Start 2:
closed
contact = start reverse
DI “Start 2”
Start 1
Start 2
Freq. Out
2
1
Figure 7-6. Start forward/Start reverse
The first selected direction has the highest priority.
When the DIN1 contact opens the direction of rotation starts the change.
1
“Start –
Rev”
- Start command
–
Direction command
Start 1: closed contact = start
open contact = stop
Start 2: closed contact = reverse
open contact = forward
Start 1
Start 2
Freq. Out
Figure 7-7. Start, Stop, Reverse
2
“Start –
Enable” –
Start command
–
Run Enable
DIN1: closed contact = start
open contact = stop
DIN2: closed contact = start enabled open contact = start disabled and drive stopped
if running