Lift Application – Parameter lists
vacon
•
5
24-hour s358 (0)40 837 1150 • Email: [email protected]
3.
LIFT APPLICATION – PARAMETER LISTS
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 13 to 40.
Column explanations:
Code
= Location indication on the keypad; Shows the operator the present param.
Number
Parameter
= Name of parameter
Min
= Minimum value of parameter
Max
= Maximum value of parameter
Unit
= Unit of parameter value; Given if available
Default
= Value preset by factory
Cust
= Customer’s own setting
ID
= ID number of the parameter (used with PC tools)
= On the parameter code: parameter value can only be changed after the FC has
been stopped.
3.1
Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See Vacon NXL User’s Manual, Chapter 7.4.1 for more information.
Code
Parameter
Unit
ID
Description
V1.1
Output frequency
Hz
1
Output frequency to motor
V1.2
Frequency reference
Hz
25
Frequency reference to motor control
V1.3
Motor speed
rpm
2
Motor speed in rpm
V1.4
Motor current
A
3
Measured motor current
V1.5
Motor torque
%
4
In % of the nominal motor torque
V1.6
Motor power
%
5
Motor shaft power
V1.7 Motor
voltage
V
6 Calculated motor voltage
V1.8
DC link voltage
V
7
Measured DC-link voltage
V1.9 Unit
temperature
°
C
8 Heatsink
temperature
V1.10
Analogue input 1
13
AI1, used as digital input DIN4
V1.11
Analogue input 2
14
AI2, used as digital input DIN5
V1.12 Analogue
I
out
mA
26
AO1
V1.13
DIN1, DIN2, DIN3
15
Digital input statuses
V1.14
DIE1, DIE2, DIE3
33
I/O Expander board: Digital input statuses
V1.15
RO1, ROE1, DOE1
1720
Relay and digital output statuses
V1.16
Lift Speed
m/s
1719
Lift speed in m/s
Table 3-1. Monitoring values