2.6 INPUT
SIGNALS
2.6.1
Start/Stop logic selection
0 DIN1: closed contact = start forward (rising edge pulse is required)
DIN2: closed contact = start reverse (rising edge pulse is required)
Figure 8. Start forward/Start reverse
c
If both DIN switches are ON at the same time the second input is ignored.
d
The drive can be re-started when both DIN switches are in OFF position.
1 DIN1: closed contact = start
open contact = stop
DIN2: closed contact = reverse
open contact = forward
Figure 9. Start, Stop, Reverse
2 DIN1: closed contact = start forward
DIN2: closed contact = start reverse
Same as selection 0 except rising edge pulse is not required.
Fault is not activated if both DIN switches are on.