7.4 Using the Vacon 50X Program Sequencer
The Vacon 50X AC drive offers functionality that allows users to program up to nine independent operation
states of the drive. This functionality is called the “program sequencer” because it allows the drive to se-
quence through the operation states programmed by the user. The Vacon 50X Program Sequencer can be
used in applications that would normally require external intelligence, such as a simple programmable
logic controller.
7.4.1 Enabling the Vacon 50X Program Sequencer
The Vacon 50X Program Sequencer can be enabled with parameter 491 (Seq Appl), found in the Applica-
tion Macro programming mode of the Vacon 50X keypad. This parameter configures:
•
Whether the sequencer is enabled,
•
The time base used for all timing of the sequencer,
•
Whether other sequencer parameters are visible in Level 2 programming.
Table 2 shows the options for this parameter:
7.4.2 Controlling the Vacon 50X Program Sequencer
The Program Sequencer can be activated and controlled from either the keypad or the terminal strip. It
is not possible to control the sequencer through the serial link. The control method of the program se-
quencer is determined by parameter 201, Input Mode. Setting the Input Mode parameter also allows
switching from Sequencer mode to normal keypad operation by way of the Local/Remote switch. Table 3
illustrates possible program sequencer control configurations.
NOTE:
If Input Mode is configured to any of the EMOP options, the sequencer is not available.
Options
Value
Meaning
Disabled
0
The Sequencer mode of the Vacon 50X is not active and the sequencer
parameters are not visible in Level 2 programming.
1 sec base
1
The Sequencer mode of the Vacon 50X is active, sequencer parameters are
visible in Level 2, and all timing for the sequencer will be on a 1-second base.
0.1 sec base
2
The Sequencer mode of the Vacon 50X is active, sequencer parameters are
visible in Level 2, and all timing for the sequencer will be on a .1-second
base.
0.01 sec base
3
The Sequencer mode of the Vacon 50X is active, sequencer parameters are
visible in Level 2, and all timing for the sequencer will be on a .01-second
base.
Table 24:Seq Appl Parameter Options
Input Mode
Setting
Input Mode
Value
Local Operation
Remote Operation
Local Only
0
Sequencer control via keypad (FWD/Stop).
Default Seq Ref is keypad
N/A
Remote Only
1
N/A
Seq control via FWD terminal.
Default Seq Ref is “Ref Select”
L/R Rem Ref
2
Normal Vacon 50X keypad operation
(Sequencer disabled)
Seq control via keypad (FWD/
Stop).
Default Seq Ref is “Ref Select”
L/R Rem Ctl
3
Normal Vacon 50X keypad operation
(Sequencer disabled)
Seq control via FWD terminal.
Default Seq Ref is keypad
L/R Rem Bth
4
Normal Vacon 50X keypad operation
(Sequencer disabled)
Seq control via FWD terminal.
Default Seq Ref is “Ref Select”
EMOP
5
Sequencer not enabled
Sequencer not enabled
EMOP2
6
Sequencer not enabled
Sequencer not enabled
LOC/EMOP
7
Sequencer not enabled
Sequencer not enabled
LOC/EMOP2
8
Sequencer not enabled
Sequencer not enabled
Table 25:Program Sequencer Control Configuration
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......