The PI Feedback parameter configures the feedback signal to be used in PI control.
The following data values may be assigned to this parameter:
Parameter Value
Description
Vin1
Vin1 is the PI feedback.
Cin
Cin is the PI feedback.
Vin2
Vin2 is the PI feedback.
The PI Proportional Gain parameter configures the proportional gain that is applied to the
PI control.
NOTE: Value must be greater than 0 for this to be active.
The PI Integral Gain parameter configures the integral gain that is applied to the PI con-
trol.
NOTE: Value must be greater than 0 for this to be active.
The PI Feed Gain parameter allows the feedback signal to be scaled. A setting of 1000 in-
dicates 100.0%.
Both the PI Error 1 and PI Error 2 parameters are read-only; they provide feedback on
how the PI control is operating.
This parameter sets the high limit of the PI output.
This parameter sets the low limit of the PI output.
851 PI Feedback
Default: Vin1
Range: Text string
Level 2
852 PI Prop Gain
Default: 0
Range: 0–2000
Level 2
853 PI Int Gain
Default: 0
Range: 0–10000
Level 2
854 PI Feed Gain
Default: 1000
Range: 0–2000
Level 2
855 PI Error 1
856 PI Error 2
Default: Read-Only
Range: 0.00–100.00%
Level 2
857 PI High Corr
Default: 100.00%
Range: 0.00–100.00%
Level 2
858 PI Low Corr
Default: 0.00%
Range: 0.00–100.00%
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......