73
vacon
vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
For example, if parameter 504 is set to 2.5 Hz and parameter 508 (Skip Freq 4) is set to
55 Hz, a skip band from 52.5 to 57.5 Hz is established.
The Rated Motor Voltage parameter configures the rated motor voltage, and allows a
user to enter the rated voltage from the motor nameplate to provide optimal control and
protection. This is usually the amount of voltage delivered to the motor terminals at the
setting of 503 (V/Hz Knee Freq).
The Rated Motor FLA parameter allows a user to enter the rated FLA from the motor
nameplate to provide optimal control and protection. This parameter should be config-
ured to the value on the nameplate of the motor, as that value is used in calculating the
percentage of current at which the drive is operating.
For information on motor timed overload operation, and how Parameter 610 works with
it, see page 78.
This parameter replaces the slip compensation parameter setting of the drive so the user
does not need to calculate it.
When parameter 501, V/Hz Select, is configured to “Linear 2pc,” this parameter, together
with parameter 513, Midpoint Volt, defines an additional point in the V/Hz characteristic.
When parameter 501, V/Hz Select, is configured to “Linear 2pc,” this parameter, along
with parameter 512, Midpoint Freq, defines an additional point in the V/Hz characteristic.
This parameter allows direct entry of the Stator Resistance (Rs) of the motor for better
vector performance. The motor manufacturer can provide this information, or you can
physically measure this value with an ohmmeter. From the line-to-line measurement of
motor resistance, enter half the measured value. (See page 46 for more information.)
This parameter allows direct entry of the motor’s power factor for better vector perfor-
mance. The motor manufacturer can provide this information.
509 Rated Mtr Volt
Default: Model dependent
Range: 100–690 V
Level 2, Macro
510 Rated Mtr FLA
Default: ND Rating
Range: 50–200% of ND rating
Level 2, Macro
511 Rated Mtr RPM
Default: 1450 rpm
Range: 0–24000 rpm
Level 2, Macro
512 Midpoint Freq
Default: 50.0 Hz
Range: 0.0 Hz–V/Hz Knee Freq
Level 2
513 Midpoint Volt
Default: 100.0%
Range: 0.0–100.0%
Level 2
514 Motor RS
Default: Model dependent
Range: 0.00–655.35 Ohms
Level 2, Macro
515 Power Factor
Default: 0.80
Range: 0.50–1.00
(0.5 times the measured line to line
resistance of motor)
Level 2, Macro
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......