21
vacon
receiving and installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
3
3.4 Cover Assembly and Torque Specifications
Figure 7 shows the locations of the Vacon 50X cover screws. The torque range for the Size 0 and 1 covers
is 2–3 Nm (18–26 in/lbs).
Figure 7: Vacon 50X Cover Assembly and Screw Locations
Torque specifications for control terminals and power terminals are listed in “General Wiring Informa-
tion” on page 23.
3.5 Serial Number Label
To determine if your drive is within the warranty time frame, find the bar code label or look in the lower
left of the technical nameplate. The serial number can be broken down as follows:
•
yywwxxxx = yy ... year of manufacture
•
ww ... week of manufacture
•
xxxx....sequential number drive during that week.
3.6 Conduit Usage
The Vacon 50X drive in the IP66 enclosure is rated for 70 bar washdown from 15 cm. To keep this rating,
the use of a sealed conduit is required. The use of a Romex-type conduit will not prevent water entry into
the enclosure. If the approved conduit is not used, all warranty claims against water damage will be void.
3.7 Condensation
The washdown process of an Vacon 50X drive may create a temperature and humidity change in and
around the drive. If the unit is mounted in a cool environment and washed down with higher-temperature
water, as the drive cools to room temperature, condensation can form inside the drive, especially around
the display. To prevent this from happening, avoid using sealed connectors around rubbercoated cables
to seal the drive. These do not allow any air transfer and hence create a level of condensation and humid-
ity that exceeds the drive’s rating.
Cover screw locations
Cover screw locations
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......