parameter descriptions
9
9.8 Digital outputs (Control panel: Menu PAR -> P8)
8.1
RO1
SIGNAL
SELECTION
8.2
RO2
SIGNAL
SELCETION
8.3
DO1
SIGNAL
SELCETION
Table 9.2: Output signals via RO1, RO2 and DO1
Setting
Signal content
0 =
Not used
Output is not in operation.
1 =
Ready
The frequency converter is ready to operate.
2 =
Run
The frequency converter operates (motor is running).
3 =
Fault
A fault trip has occurred.
4 =
Fault inverted
A fault trip has not occurred.
5 =
Warning
A warning is active.
6 =
Reversed
The reverse command has been selected, output fre-
quency to the motor is negative.
7 =
At speed
The output frequency has reached the set reference.
8 =
Motor regulator active
Each of Motor regulator is active (e.g., over current
regulator, over voltage regulator, under voltage reg-
ulator, etc.)
9 =
FB Control Word.B13
Output can be controlled with B13 in the fieldbus control
word.
10 =
FB Control Word.B14
Output can be controlled with B14 in the fieldbus control
word.
11 =
FB Control Word.B15
Output can be controlled with B15 in the fieldbus control
word.
12 =
Output frequency superv.
Output frequency is over / under the limits, set with
parameters P12.1 and P12.2.
13 =
Output torque superv.
Motor torque is over/under the limit, se t with parameter
P12.3 and P12.4
14 =
Unit temperature superv.
Unit temperature is over / under the limits, set with
parameters P12.5 and P12.6.
15 =
Analogue input superv.
Analogue inputs set with parameter P12.7 is over / under
the limits, set in P12.8 and P12.9.
16 =
Preset Speed Active
Each of preset speeds are activated.
17 =
External Brake control
External Brake control. Closed = Brake open,
Open = Brake closed.
18 =
Keypad control active
Keypad is set as the current control place.
19 =
I / O control active
I / O is set as the current control place.
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...