vacon • 25
Description of Groups
3
3.3.6
Group Analogue outputs: Menu PAR G6
Code
Parameter
Min
Max
Unit
Default
ID
Description
P6.1
Analogue output
function
0
8
2
307
0 = Not used (fixed 100%)
1 = Freq. reference (0-fmax)
2 = Output freq. (0 -fmax)
3 = Motor speed (0 - Speed
max)
4 = Output current (0-InMotor)
5 = Motor torque (0-TnMotor)
6 = Motor power (0-PnMotor)
7 = PID output (0-100%)
8 = Filedbus(0-10000)
P6.2
Analogue output
minimum
0
1
0
310
0 = 0V
1 = 2V
P6.3
Analogue output scale
0,0
1000,0
%
100.0
311
Scaling factor
P6.4
Analogue output filter
time
0.00
10.00
s
0.10
308
Filtering time of analogue out-
put signal.
0 = No filtering
Table 12. Analogue outputs group.