Monitoring Menu
vacon • 64
Service support: find your nearest Vacon service center at www.vacon.com
5
5.1.8
ExtPID Controller
5.1.9
Mainten. counters
5.1.10
Fieldbus data
Table 40. External PID Controller value monitoring
Code
Monitoring value
Unit
Scale
ID
Description
V2.9.1
ExtPID setpoint
Varies
According to
P3.14.1.10
83
External PID controller setpoint value in
process units. Process unit is selected with
a parameter.
V2.9.2
ExtPID feedback
Varies
According to
P3.14.1.10
84
External PID controller feedback value in
process units. Process unit is selected with
a parameter.
V2.9.3
ExtPID error
Varies
According to
P3.14.1.10
85
External PID controller Error value. Devia-
tion of feedback from setpoint in process
units. Process unit is selected with a
parameter.
V2.9.4
ExtPID output
%
0.01
86
External PID controller outputin percent
(0..100%). This value can be fed e.g. to Ana-
logue output.
V2.9.5
ExtPID status
1
87
0=Stopped
1=Running
4=In dead band
Table 41. Maintenance counter monitoring
Code
Monitoring value
Unit
Scale
ID
Description
V2.11.1
MaintenCounter 1
h/ kRev
Varies
1101
Status of maintenance counter in revolutions
multiplied by 1000, or hours.
For configuration and activation of this coun-
ter, see chapter Group 3.16: Maintenance
counters.
Table 42. Fieldbus data monitoring
Code
Monitoring
value
Unit
Scale
ID
Description
V2.12.1
FB Control Word
1
874
Fieldbus control word used by application in
bypass mode/format. Depending on the fieldbus
type or profile the data can be modified before
sent to application.
V2.12.2
FB Speed Refer-
ence
Varies
875
Speed reference scaled between minimum and
maximum frequency at the moment it was
received by the application. Minimum and maxi-
mum frequencies can be changed after the refer-
ence was received without affecting the reference.
V2.12.3
FB data in 1
1
876
Raw value of process data in 32-bit signed format
V2.12.4
FB data in 2
1
877
Raw value of process data in 32-bit signed format
V2.12.5
FB data in 3
1
878
Raw value of process data in 32-bit signed format
V2.12.6
FB data in 4
1
879
Raw value of process data in 32-bit signed format
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......