Programming
vacon • 16
24-hour s358 (0)40 837 1150 • Email: [email protected]
5
5.
P
ROGRAMMING
Basic information on how to use the control keypad you will find in the Vacon HVAC Drive Application
Manual (publication DPD00039).
The navigation path to the fieldbus parameters may differ from application to application. The
exemplary paths below apply to the Vacon 100 HVAC drive.
1.
First ensure that the right fieldbus protocol is selected.
2.
Select
‘Fieldbus control’
as the
Remote Control Place
.
3.
Choose source of reference.
4.
Set fieldbus parameters (M5.7 and M5.8). See below.
5.1
Modbus RTU parameters and monitoring values (M5.7.3)
Code
Parameter
Min
Max
Unit
Default
ID
Description
PARAMETERS
P5.7.3.1.1
Slave address
1
247
1
Unique slave device
address.
P5.7.3.1.2
Baud rate
1
9
bd
6
2236
Communication speed
1 = 300
2 = 600
3 = 1200
4 = 2400
5 = 4800
6 = 9600
7 = 19200
8 = 38400
9 = 57600
P5.7.3.1.3
Parity type
0
2
0
2239
0 = None
1 = Odd
2 = Even
P5.7.3.1.4
Communication
time-out
0
65535
s
10
0 = Not used
Navigate: Main Menu > I/O and Hardware (M5) > RS-485 (M5.7)
OR
Ethernet
(M5.8) > Common settings (M5.7.1) > Protocol (P5.7.1.1) > Edit >
(Choose protocol)
Navigate: Main Menu > Quick Setup (M1) > Rem. Ctrl. Place (P1.15)
OR
Navigate: Main Menu > Parameters (M3) > Start/Stop Setup (M3.2) > Rem.
Ctrl. Place (P3.2.1)
Navigate: Main Menu > Parameters (M3) > References (M3.3)
Содержание 100 INDUSTRIAL
Страница 1: ......
Страница 3: ...vacon 1 Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 7: ...1 vacon 5 Safety Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 11: ...3 vacon 9 Modbus technical data Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 27: ...5 vacon 25 Programming Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 43: ...7 vacon 41 Fault tracing Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 45: ...8 vacon 43 Quick setup Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 47: ......