vacon • 22
Installation
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3.8
Power ratings
Table 12. AC drive (208…240 V 3AC 50/60 Hz, up to 400 V DC) output ratings
Enclosure
size
AC
drive
type
Voltage
(nominal
or
range)
[V AC]
Current
(maximum
continuous)
[A AC]
Current
(inrush)
[A AC]
(2 s)
Frequency
(nominal
or range
[Hz]
Power
(maximum
continuous)
[W]
(230 V)
Power
factor
range
Max.
output
fault
current
[A AC]
Max.
output
over
current
protection
[A AC]
MM4
0006
0-240
6.6
13.2
0-320
1100
0.3-1
19.9
19.9
0008
0-240
8.0
16.0
0-320
1500
0.3-1
26.3
26.3
0011
0-240
11.0
22.0
0-320
2200
0.3-1
33.1
33.1
0012
0-240
12.5
25.0
0-320
3000
0.3-1
39.8
39.8
MM5
0018
0-240
18.0
36.0
0-320
4000
0.3-1
72.3
72.3
0024
0-240
24.2
48.4
0-320
5500
0.3-1
72.3
72.3
0031
0-240
31.0
62.0
0-320
7500
0.3-1
91.1
91.1
MM6
0048
0-240
48.0
96.0
0-320
11000
0.3-1
154.3
154.3
0062
0-240
62.0
124.0
0-320
15000
0.3-1
185.7
185.7
MR5
0018
0-240
18.0
25.0
0-320
4000
0.3-1
50.0
50.0
0024
0-240
24.0
36.0
0-320
5500
0.3-1
72.0
72.0
0031
0-240
31.0
46.0
0-320
7500
0.3-1
100.0
100.0
MR6
0048
0-240
48.0
62.0
0-320
11000
0.3-1
124.0
124.0
0062
0-240
62.0
96.0
0-320
15000
0.3-1
192.0
192.0
MR7
0075
0-240
75.0
124.0
0-320
18500
0.3-1
248.0
248.0
0088
0-240
88.0
150.0
0-320
22000
0.3-1
300.0
300.0
0105
0-240
105.0
176.0
0-320
30000
0.3-1
352.0
352.0
MR8
0140
0-240
140.0
210.0
0-320
37000
0.3-1
456.0
456.0
0170
0-240
170.0
280.0
0-320
45000
0.3-1
560.0
560.0
0205
0-240
205.0
340.0
0-320
55000
0.3-1
680.0
680.0
MR9A
0261
0-240
261.0
410.0
0-320
75000
0.3-1
844.0
844.0
0310
0-240
310.0
502.0
0-320
90000
0.3-1
1004.0
1004.0