Table 19: The default values for Process Data Out in fieldbus
Data
Default value
Scale
Process Data Out 1
Output frequency
0.01 Hz
Process Data Out 2
Motor speed
1 rpm
Process Data Out 3
Motor current
0.1 A
Process Data Out 4
Motor torque
0.1%
Process Data Out 5
Motor power
0.1%
Process Data Out 6
Motor voltage
0.1 V
Process Data Out 7
DC link voltage
1 V
Process Data Out 8
Last active fault code
1
For example, the value 2500 for Output frequency agrees with 25.00 Hz, because the scale is
0.01. All the monitoring values that you can find in Chapter 4.1 Monitor group are given the
scale value.
5.7
GROUP 3.7: PROHIBIT FREQUENCIES
Table 20: Prohibit frequencies
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.7.1
Prohibit Frequency
Range 1 Low Limit
-1.00
320.00
Hz
0.00
509
0 = Not used
P3.7.2
Prohibit Frequency
Range 1 High Limit
0.00
320.00
Hz
0.00
510
0 = Not used
P3.7.3
Prohibit Frequency
Range 2 Low Limit
0.00
320.00
Hz
0.00
511
0 = Not used
P3.7.4
Prohibit Frequency
Range 2 High Limit
0.00
320.00
Hz
0.00
512
0 = Not used
P3.7.5
Prohibit Frequency
Range 3 Low Limit
0.00
320.00
Hz
0.00
513
0 = Not used
P3.7.6
Prohibit Frequency
Range 3 High Limit
0.00
320.00
Hz
0.00
514
0 = Not used
P3.7.7
Ramp Time Factor
0.1
10.0
Times
1.0
518
VACON · 70
PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205