9
Set the signal range of the analogue input
0 = 0-10V / 0-20mA
1 = 2-10V / 4-20mA
See Table 15 Analogue input settings.
10
Set a value for Keypad Setpoint 1 (P3.12.2.1) and
Keypad Setpoint 2 (P3.12.2.2)
Depends on the range set in the question 9.
11
Using the sleep function
0 = No
1 = Yes
If you give the value Yes for the question 11, you see the next 3 questions. If you give the value
No, the wizard is completed.
12
Set a value for Sleep Frequency Limit (P3.12.2.7)
Range: 0.00-320.00 Hz
13
Set a value for Sleep Delay 1 (P3.12.2.8)
Range: 0-3000 s
14
Set a value for Wake-up Level (P3.12.2.9)
The range depends on the set process unit
The PID mini-wizard is completed.
2.2
MULTI-PUMP MINI-WIZARD
The Multi-pump mini-wizard asks the most important questions to set up a Multi-pump
system. The Multi-pump mini-wizard always follows the PID mini-wizard.
15
Set a value for Number of Motors (P.3.14.1)
1-4
16
Set a value for Interlock Function (P3.14.2)
0 = Not used
1 = Enabled
17
Set a value for Autochange (P3.14.4)
0 = Disabled
1 = Enabled
If you enable the Autochange function, you see the next 3 questions. If you do not use the
Autochange function, the wizard goes directly to question 21.
WIZARDS
VACON · 21
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]