29
Set a value for P3.15.7 Autochanged pumps
0 = Auxiliary pumps
1 = All pumps
Step 30 shows only if you set the value Enabled (Interval) to parameter Autochange in step 28.
30
Set a value for P3.15.8 Autochange Interval
Range: 0-3000 h
Steps 31 and 32 show only if you set the value Enabled (Weekdays) to parameter Autochange
in step 28.
31
Set a value for P3.15.9 Autochange Days
Range: Monday to Sunday
32
Set a value for P3.15.10 Autochange Time of Day
Range: 00:00:00 to 23:59:59
33
Set a value for P3.15.11 Autochange Frequency
Limit
Range: P3.3.1.1-P3.3.1.2 Hz
34
Set a value for P3.15.12 Autochange Pump Limit
Range: 1-8
35
Set a value for P3.15.13 Bandwidth
Range: 0-100%
36
Set a value for P3.15.14 Bandwidth Delay
Range: 0-3600 s
The Multi-pump (single drive) application wizard is completed.
2.5
MULTI-PUMP (MULTIDRIVE) APPLICATION WIZARD
The application wizard helps you to set the basic parameters that are related to the
application.
To start the Multi-pump (multidrive) application wizard, set the value Multi-pump (Multidrive)
to parameter P1.2 Application (ID 212) in the keypad.
NOTE!
If you start the application wizard from the Startup wizard, the wizard goes directly
to step 11.