11
Set a value for P3.4.1.2 Acceleration Time 1
Range: 0.1-3000.0 s
12
Set a value for P3.4.1.3 Deceleration Time 1
Range: 0.1-3000.0 s
Next the wizard goes to steps that are specified by the application.
13
Select the control place (where you give the start
and stop commands and the frequency reference)
I/O Terminal
Fieldbus
Keypad
The HVAC application wizard is completed.
Table 14: Preset values of parameters
Index
Parameter
Process type
Pump
Fan
Compressor
P3.1.4.1
U/f Ratio
Linear
Squared
Linear
P3.2.4
Start Function
Ramping
Flying start
Ramping
P3.2.5
Stop Function
Ramping
Coasting
Ramping
P3.4.1.2
Acceleration Time
5.0 s
30.0 s
3.0 s
P3.4.1.3
Deceleration Time
5.0 s
30.0 s
3.0 s
2.3
PID CONTROL APPLICATION WIZARD
The application wizard helps you to set the basic parameters that are related to the
application.
To start the PID control application wizard, set the value PID control to parameter P1.2
Application (ID 212) in the keypad.
NOTE!
If you start the application wizard from the Startup wizard, the wizard goes directly
to step 11.
WIZARDS
VACON · 79
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
2