CAUTION!
Do not use the quick stop function as an emergency stop. An emergency stop must
stop the power supply to the motor. The quick stop function does not do this.
OR
IN 1
IN 2
FB
I/O
Yes
Control Word B12
Quick Stop Activ.
Normal
operation
Start stop
sequence
according to
Quick Stop Mode
and Quick Stop
Deceleration
Time
Quick Stop
Activated
Quick Stop
Activated
NO
Drive
stopped?
Yes
Drive forced to
Not Ready status
and alarm/fault
triggered
according to
Quick Stop Fault
Fig. 72: The quick stop logic
10.10.6 AI LOW PROTECTION
P3.9.8.1 ANALOGUE INPUT LOW PROTECTION (ID 767)
Use this parameter to select when the AI Low supervision is enabled.