5.10
GROUP 3.10: AUTOMATIC RESET
Table 64: Autoreset settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.10.1
Automatic Reset
0
1
0 *
731
0 = Disabled
1 = Enabled
P3.10.2
Restart Function
0
1
1
719
0 = Flying start
1 = According to P3.2.4.
P3.10.3
Wait Time
0.10
10000.0
0
s
0.50
717
P3.10.4
Trial Time
0.00
10000.0
0
s
60.00
718
P3.10.5
Number of Trials
1
10
4
759
P3.10.6
Autoreset: Under-
voltage
0
1
1
720
0 = No
1 = Yes
P3.10.7
Autoreset: Overvolt-
age
0
1
1
721
0 = No
1 = Yes
P3.10.8
Autoreset: Overcur-
rent
0
1
1
722
0 = No
1 = Yes
P3.10.9
Autoreset: AI Low
0
1
1
723
0 = No
1 = Yes
P3.10.10 Autoreset: Unit Over-
temperature
0
1
1
724
0 = No
1 = Yes
P3.10.11
Autoreset: Motor
Overtemperature
0
1
1
725
0 = No
1 = Yes
P3.10.12
Autoreset: External
Fault
0
1
0
726
0 = No
1 = Yes
P3.10.13
Autoreset: Under-
load Fault
0
1
0
738
0 = No
1 = Yes
P3.10.14
Autoreset: PID
Supervision Fault
0
1
0
776
0 = No
1 = Yes
P3.10.15
Autoreset: Ext PID
Supervision Fault
0
1
0
777
0 = No
1 = Yes
* The selection of the application with parameter P1.2 Application gives the default value.
See the default values in 12.1 The default values of parameters in the different applications.
VACON · 158
PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/