5.5
GROUP 3.5: I/O CONFIGURATION
Table 43: Digital input settings
Index
Parameter
Default
ID
Description
P3.5.1.1
Control Signal 1 A
DigIN SlotA.1 *
403
P3.5.1.2
Control Signal 2 A
DigIN SlotA.2 *
404
P3.5.1.3
Control Signal 3 A
DigIN Slot0.1
434
P3.5.1.4
Control Signal 1 B
DigIN Slot0.1 *
423
P3.5.1.5
Control Signal 2 B
DigIN Slot0.1
424
P3.5.1.6
Control Signal 3 B
DigIN Slot0.1
435
P3.5.1.7
I/O B Control Force
DigIN Slot0.1 *
425
P3.5.1.8
I/O B Reference Force
DigIN Slot0.1 *
343
P3.5.1.9
Fieldbus Control Force
DigIN Slot0.1 *
411
P3.5.1.10
Keypad Control Force
DigIN Slot0.1 *
410
P3.5.1.11
External Fault Close
DigIN SlotA.3 *
405
OPEN = OK
CLOSED = External fault
P3.5.1.12
External Fault Open
DigIN Slot0.2
406
OPEN = External fault
CLOSED = OK
P3.5.1.13
Fault Reset Close
Varies
414
CLOSED = Resets all active faults.
P3.5.1.14
Fault Reset Open
DigIN Slot0.1
213
OPEN = Resets all active faults.
P3.5.1.15
Run Enable
DigIN Slot0.2
407
P3.5.1.16
Run Interlock 1
DigIN Slot0.2
1041
OPEN = Start not permitted
CLOSED = Start permitted
P3.5.1.17
Run Interlock 2
DigIN Slot0.2
1042
As above.
P3.5.1.18
Motor Preheat ON
DigIN Slot0.1
1044
OPEN = No action.
CLOSED = Uses the DC current of the
motor preheat in the Stop state. Used
when the value of P3.18.1 is 2.
P3.5.1.19
Ramp 2 Selection
DigIN Slot0.1
408
OPEN = Ramp 1 Shape, Acceleration
Time 1 and Deceleration Time 1.
CLOSED = Ramp 2 Shape, Accelera-
tion Time 2 and Deceleration Time 2.
P3.5.1.20
Acc/Dec Prohibit
DigIN Slot0.1
415
P3.5.1.21
Preset Frequency Selection 0
DigIN SlotA.4 *
419
P3.5.1.22
Preset Frequency Selection 1
Varies
420
VACON · 138