Table 37: Flushing parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.6.1
Flushing Reference
Activation
DigIN
Slot0.1 *
530
P3.3.6.2
Flushing reference
-MaxRef MaxRef
Hz
0.00 *
1239
* The default value of the parameter is specified by the application that you select with
parameter P1.2 Application. See the default values in Chapter 12.1 The default values of
parameters in the different applications.
5.4
GROUP 3.4: RAMPS AND BRAKES SETUP
Table 38: Ramp 1 setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.4.1.1
Ramp 1 Shape
0.0
100.0
%
0.0
500
P3.4.1.2
Acceleration Time 1
0.1
3000.0
s
5.0
103
P3.4.1.3
Deceleration Time 1
0.1
3000.0
s
5.0
104
Table 39: Ramp 2 setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.4.2.1
Ramp 2 Shape
0.0
100.0
%
0.0
501
P3.4.2.2
Acceleration Time 2
0.1
3000.0
s
10.0
502
P3.4.2.3
Deceleration Time 2
0.1
3000.0
s
10.0
503
P3.4.2.4
Ramp 2 Selection
Varies
Varies
DigIN
Slot0.1
408
OPEN = Ramp 1 Shape,
Acceleration Time 1
and Deceleration Time
1.
CLOSED = Ramp 2
Shape, Acceleration
Time 2 and Decelera-
tion Time 2.
P3.4.2.5
Ramp 2 Threshold
Frequency
0.0
P3.3.1.2
Hz
0.0
533
0 = Not used
VACON · 136
PARAMETERS MENU
5