5.2
GROUP 3.2: START/STOP SETUP
Table 33: Start/stop setup menu
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.2.1
Remote Control
Place
0
1
0 *
172
0 = I/O control
1 = Fieldbus control
P3.2.2
Local/Remote
0
1
0 *
211
0 = Remote
1 = Local
P3.2.3
Keypad Stop Button
0
1
0
114
0 = Yes
1 = No
P3.2.4
Start Function
0
1
0
505
0 = Ramping
1 = Flying start
P3.2.5
Stop Function
0
1
0
506
0 = Coasting
1 = Ramping
P3.2.6
I/O A Start/Stop
Logic
0
4
2 *
300
Logic = 0
Ctrl sgn 1 = Forward
Ctrl sgn 2 = Backward
Logic = 1
Ctrl sgn 1 = Forward
(edge)
Ctrl sgn 2 = Inverted
Stop
Ctrl sgn 3 = Bckwrd
(edge)
Logic = 2
Ctrl sgn 1 = Forward
(edge)
Ctrl sgn 2 = Bckwrd
(edge)
Logic = 3
Ctrl sgn 1 = Start
Ctrl sgn 2 = Reverse
Logic = 4
Ctrl sgn 1 = Start
(edge)
Ctrl sgn 2 = Reverse
P3.2.7
I/O B Start/Stop
Logic
0
4
2 *
363
See above.