Table 23: Multi-pump monitoring
Index
Monitoring value
Unit
Scale
ID
Description
V2.10.1
Motors Running
1
30
V2.10.2
Autochange
1
1114
V2.10.3
Next Autochange
h
0.1
1503
V2.10.4
Operate Mode
1
1505
0 = Slave
1 = Master
V2.10.5
Multi-pump Status
1
1628
0 = Not used
10 = Stopped
20 = Sleep
30 = Anti-blocking
40 = Auto-cleaning
50 = Flushing
60 = Soft filling
70 = Regulating
80 = Following
90 = Const. producing
200 = Unknown
V2.10.6
Communication
Status
h
0.1
1629
0 = Not used (Multi-pump multidrive function)
10 = Fatal communication errors occurred
(or no communication)
11 = Errors occurred (data sending)
12 = Errors occurred (data receiving)
20 = Communication operational, no errors
occurred
30 = Status unknown
V2.10.7
Pump (1) Running
Time
h
0.1
1620
V2.10.8
Pump 2 Running
Time
h
0.1
1621
V2.10.9
Pump 3 Running
Time
h
0.1
1622
V2.10.10
Pump 4 Running
Time
h
0.1
1623
V2.10.11
Pump 5 Running
Time
h
0.1
1624
V2.10.12
Pump 6 Running
Time
h
0.1
1625
V2.10.13
Pump 7 Running
Time
h
0.1
1626
V2.10.14
Pump 8 Running
Time
h
0.1
1627
VACON · 124