Mounting
3 Mounting
Caution - Risk of injury!
Incorrect parameter values can cause the valve to move unexpectedly. This can lead to
process failures and result in injuries.
Before recommissioning a
D400
positioner that was used at another
location, the device must always be reset to factory settings. Never start Autoadjust before
restoring factory settings.
3.1
Operating conditions at installation site
Important
Before installation, check whether the
D400
positioner meets the
control and safety requirements for the installation location (actuator or valve).
See the „Specifications“ chapter in the operating instructions or on the data sheet.
3.2
Mechanical mount
3.2.1 General
Fig. 1: Operating range
The arrow (1) on the positioner feedback shaft (and the lever) must move through the area
marked by the arrows (2).
8 - EN D400 CI/TZIDC/110/120-EN