6
C-00829 USJJ-005 Manual Rev. 6.5 (8-15-14)
Installation for 15 kV SMD-20 Power Fuse ONLY
1. Grasp the top perpendicular ring of the Jack Jumper™ Cutout Bypass Tool with the
shotgun stick.
2. Extend the shotgun stick as needed and per its instruction.
3. Attach the upper attachment hook to the upper fuse door (Figure C).
4. Be sure the Jack Jumper™ Cutout Bypass Tool is secure and will not interfere with
removal of the fuse.
5. Release the top ring.
6. Grasp the bottom in-line ring of the Jack Jumper™ Cutout Bypass Tool with the
shotgun stick.
7. Gently pull to expand the spring and hook the bottom attachment hook on the lower
fuse door hinge casting (Figure D). The Jack Jumper™ Cutout Bypass Tool is now in
place; release it from the shotgun stick.
For 200 Ampere SMD-20 systems attach two Jack Jumper™ Cutout Bypass
Tools on opposite sides of the SMD-20 Power Fuse (this only works for SMD-20
Power Fuse Tools and cannot be utilized for standard cutouts).
8. Open the fuse door and replace as necessary.
Upper Attachment Point
SMD-20 Systems
Figure C
Lower Attachment Point
SMD-20 Systems
Figure D
Upper Fuse
Door
Lower Fuse
Door
Fuse
WARNING
!
!
Do not attach to the Arcing
Horns on an SMD-20 unit.
Содержание Jack Jumper SMD-20
Страница 8: ...8 C 00829 USJJ 005 Manual Rev 6 5 8 15 14...