27
5.10 (3" /80 mm Only) Flexible Vent System
Single Wall Elbows - Equivalent Length
Vent Dia.
3" [80 mm]
45° bend
0.82 ft [0.25 m]
90° bend
1.64 ft [0.50 m]
• Maximum vent lengths based on equivalent
straight runs only. Include rigid pipe and fittings
in overall equivalent length calculations.
• Flexible venting installations use single wall
polypropylene to pass flue gasses to base of
chimney, then flexible venting to get them to
termination at the top.
• Combustion air is not supplied through masonry
chimney. Combustion air must be from outside
using 3" [80 mm] single wall polypropylene.
• Position boiler to use minimum of rigid single wall
polypropylene venting to the chimney.
• Follow venting manufacturer's instructions on
assembly and clearances to maintain.
•
Avoid sharp bends in flexible venting.
FIGURE 5-24 - (3" / 80 mm Only) Flexible Venting
System CAN BE USED ON ALL SIZES
Combustion
Air
Vent Terminal
Flexible Vent
Rigid Vent
5 - COMBUSTION AIR AND VENT PIPING
Flexible Pipe Minimum & Maximum Vent
Lengths
3” [80 mm]
Diameter Pipe
100/115/125/150
165/205
Min
Max
Min
Max
Natalini
Exhaust
6 ft
[1.8 m]
75 ft
[22.8 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft
[15.2 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
DuraVent
®
Exhaust
6 ft
[1.8 m]
82 ft
[24.9 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft
[15.2 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Centrotherm
Exhaust
6 ft
[1.8 m]
52 ft
[15.8 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
6 ft
[1.8 m]
50 ft
[15.2 m]
6 ft
[1.8 m]
50 ft
[15.2 m]
Z-Dens
Exhaust
NA
6 ft
[1.8 m]
50 ft
[15.2 m]
Intake
Flexible vent systems shall only be run
vertical. Horizontal runs before adapting
to flexible must be rigid pipe.
Note
240013371 REV B, [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...