background image

3.1

95-8452

2

In  normally  smoky  atmospheres  the  detector  will  not 

go into alarm as long as the concentration is less than 

the  fixed  sensitivity  of  the  detector.    This  results  in  a 

sensitive and positive response with the lowest potential 

for unwanted alarms.

The main enclosure of the detector contains the electronic 

circuitry, alarm relay, and supervision relay.  

FaIlSaFE OpERaTION

To ensure reliable operation, the U5005 is equipped with 

self-checking circuitry.  A regulation photodiode, which 

is matched to the smoke detection circuit, continuously 

monitors the output intensity of the IRED and adjusts it as 

necessary to compensate for an accumulation of dust or 

other contaminants, or any other variation that can occur 

with temperature and time.  A power supervision relay in 

the detector provides a trouble output signal in the event 

of an input power failure.

The  detector  uses  extensive  filtering  against  RF  and 

transient interference.  In addition, there is a 2 second 

time delay before an alarm is generated.

The printed circuit board inside the detector is coated to 

minimize the possibility of problems caused by moisture 

accumulation.

DETECTOR OUTpUTS

The  detector  provides  a  set  of  Form  A  (SPST)  NO 

contacts  for  connection  to  the  alarm  output  circuitry 

and a set of SPST NC contacts for supervision of input 

power.  An auxiliary set of Form C (SPDT) NO/NC alarm 

relay  contacts  is  also  provided  for  controlling  remote 

annunciation devices.

The  alarm  output  latches  on  in  the  event  of  an  alarm 

and an LED located on the outer surface of the housing 

is  illuminated  to  provide  a  visual  indication  that  an 

alarm condition has occurred.  The detector is reset by 

momentarily interrupting input power.

SPECIFICATIONS

OPERATING VOLTAGE—

20 to 28 Vdc filtered supply, with less than 1.4 vpp at 60 

to 120 Hz.

OPERATING CURRENT—

Standby: 

10 milliamperes.

Alarm: 

35 milliamperes.

TEMPERATURE RANGE—

Operating:  –13°F to +140°F  (–25°C to +60°C).

Storage: 

–67°F to +185°F  (–55°C to +85°C).

ALARM  AND  SUPERVISORy  RELAy  CONTACT 
RATING—

1.0 ampere at 30 Vdc, SPST.

AUXILIARy ALARM RELAy CONTACT RATING—

2.0 amperes at 30 Vdc, Form C, SPDT.

jUNCTION bOX—

Body material: 

Copper-free aluminum.

Conduit Fitting:  25 mm (female).

CERTIFICATIONS—

CSA:   

Certified for use in Class I, Division 2,  

   

Groups A, B, C and D hazardous   

   

locations.

DIMENSIONS—

See Figure 2.

wEIGhT—

2 pounds (0.91 kilogram)

INSTALLATION

The U5005 is intended for surface mounting.  See Figure 

2.  The mounting screw holes are counterbored for No. 

8  flat-head  screws.    Electrical  equipment  that  is  used 

in conjunction with the smoke detector is connected to 

the detector using a terminal strip located in the junction 

box that is furnished with the unit.

DETECTOR lOCaTION

The smoke detector is normally mounted on the ceiling not 

less than six inches from a side wall.  The exact location 

of  the  detector  must  be  determined  by  an  evaluation 

based  on  engineering  judgment  supplemented,  if 

possible, by field tests.

For  additional  information  on  detector  location  and 

spacing, contact the National Fire Protection Association, 

Batterymarch Park, Quincy, Mass. 02269, and request a 

copy  of  NFPA  Number  72,  the  Standard  on  Automatic 

Fire Detectors.

FM

APPROVED

®

Содержание DET-TRONICS U5005

Страница 1: ...taic smoke cell which is placed at an angle to the pulsed invisible light source is sensitive to the infrared light in the specified frequency emitted by the IRED light source and is designed to receive a signal only when the pulsed IRED source is activated See Figure 1 When smoke enters the chamber the light from the IRED reflects off the smoke particles and reaches the photovoltaic smoke cell Wh...

Страница 2: ...in the event of an alarm and an LED located on the outer surface of the housing is illuminated to provide a visual indication that an alarm condition has occurred The detector is reset by momentarily interrupting input power SPECIFICATIONS OPERATING VOLTAGE 20 to 28 Vdc filtered supply with less than 1 4 vpp at 60 to 120 Hz OPERATING CURRENT Standby 10 milliamperes Alarm 35 milliamperes TEMPERATUR...

Страница 3: ...ls and re install the junction box cover See Figures 3 4 and 5 for wiring details Detector Connections The U5005 contains two sets of relay contacts One set of NO Alarm contacts close upon detection 1 of smoke One set of NC Trouble contacts close when the 2 detector is powered 3 5 8 9 14 4 36 6 B1967 120 5 32 INCH DIA 3 2 4 6 1 5 3 13 5 3 46 8 8 4 7 11 9 2 7 6 9 5 2 13 2 5 86 14 9 3 77 9 6 1 28 3 ...

Страница 4: ...B 3 POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND LISTED CONTROL PANEL EOL DEVICE SUPPLIED BY PANEL MANUFACTURER ADD JUMPER GROUND STUD B1193 6 7 8 9 10 Figure 4 Single Detector Wiring Figure 5 Multiple Detector Wiring FIRST DETECTOR IN LOOP TB 2 LAST DETECTOR IN LOOP TB 2 TB 3 POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND LISTED CONTROL PANEL AUXILIARY ALARM CONTACTS C NO NC AUXILIARY A...

Отзывы: