CHIMNEY
Your wood stove may be hooked up with a factory built or masonry chimney. If you are using a fac-
tory built chimney, it must comply with UL 103 standard; therefore it must be a Type HT (2100°F). It
is extremely important that it be installed according to the manufacturer’s specifications.
If you are using a masonry chimney, it is important that it be built in compliance with the specifica-
tions of the National Building Code. It must be lined with fire clay bricks, metal or clay tiles sealed
together with fire cement. (Round flues are the most efficient).
The interior diameter of the chimney flue must be identical to the stove smoke exhaust. A flue which
is too small may cause draft problems, while a large flue favours rapid cooling of the gas, and hence
the build-up of creosote and the risk of chimney fires. Note that it is the chimney and not the stove
which creates the draft effect; your stove’s performance is directly dependent on an adequate draft
from your chimney.
The following recommendations may be useful for the installation of your chimney:
1. Do not connect this unit to a chimney flue serving another appliance.
2. Where passage through a wall, or partition of combustible construction is desired, the
installation must conform to CAN/CSA-B365
3. It must rise above the roof at least 3’ (0.9 mm) from the uppermost point of contact.
4. The chimney must exceed any part of the building or other obstruction within a 10’ (3.04m)
distance by a height of 2’ (0.6 m).
5. Installation of an interior chimney is always preferable to an exterior chimney. Indeed, the
interior chimney will, by definition, be hotter than an exterior chimney, being heated up
by the ambient air in the house. Therefore the gas which circulates will cool more slowly,
thus reducing the build-up of creosote and the risk of chimney fires.
6. The draft caused by the tendency for hot air to rise will be increased with an interior chimney.
7. Using a fire screen at the extremity of the chimney requires regular inspection in order
to insure that it is not obstructed thus blocking the draft, and it should be cleaned when
regularly.
8. The chimney and chimney connector must be kept clean and in good condition for opti-
mum performance.
Содержание Magnolia 2015
Страница 13: ...Ussc 13 TYPICAL INSTALLATIONS FACTORY BUILT CHIMNEY Wall Installation Vertical Installation ...
Страница 14: ...14 Ussc TYPICAL INSTALLATIONS continued MASONRY CHIMNEY ...
Страница 15: ...Ussc 15 TYPICAL INSTALLATIONS continued FACTORY BUILT THIMBLE BUILT THIMBLE ...
Страница 22: ...22 Ussc NOTES ...
Страница 23: ...Ussc 23 NOTES ...