REGENERATIVE DC
COMMON BUS SUPPLY
15 HP TO 1300 HP
INST
RUCTI
ON
MANU
AL
Страница 1: ...REGENERATIVE DC COMMON BUS SUPPLY 15 HP TO 1300 HP INSTRUCTION MANUAL ...
Страница 2: ...ill be subject to vibration then the enclosure should be shock mounted Safety Warnings Regenerative modules like all electrical equipment in industry if not properly installed and operated can cause personal injury Always use common sense when working around electrical equipment Make sure you read this manual before any work on the unit begins Never work on this product if you are tired or under t...
Страница 3: ...y may result in personnel injury and or equipment damage WARNING An incorrectly applied or installed AC REGEN can result in component damage or a reduction in product life Wiring or application errors such as under sizing the motor incorrect or inadequate AC supply or excessive ambient temperatures may result in damage to the Drive or motor WARNING This AC REGEN contains ESD Electrostatic Discharg...
Страница 4: ...l attributes Mounting Though hole or panel mount Nema Rating Type 1 IP20 as standard Type 12 IP54 optional Construction Steel construction reduces E M I Control I O 2 Digital Inputs Regen Enable Regen Reset 2 Digital Outputs Form C dry contacts rated 115Vac 5A 30Vdc 3 5A 1 meter output Use with 100 A movement analog meter 24Vdc source Use to power operator pushbuttons and US Drives option boards 2...
Страница 5: ...uses Ferraz Shawmut A50P A60X Bussmann FWH 4 Total Power Loss shown is for continuous operation at full regeneration Table 2 Class 400 Regenerative DC Common Bus Supply Models Typical Voltage 380 415 480 VAC 380 500VAC 10 to 10 Frame Designation NEMA 1 IP20 Catalog Number Drive HP2 Continuous Regen DC Bus Current Amps Continuous Motoring DC Bus Current Amps AC Current Amps Maximum Recommended AC L...
Страница 6: ...240 244 225 350 1538 RGB 0500 0300 N1 350 300 342 312 450 1900 RGB 0500 0360 N1 400 360 390 355 600 2282 SIZE 3 RGB 0500 0480 N1 500 480 488 439 700 3026 RGB 0500 0540 N1 600 540 586 536 800 3390 RGB 0500 0600 N1 700 600 683 625 900 3770 RGB 0500 0720 N1 800 720 781 714 1000 4514 RGB 0500 0840 N1 900 840 878 804 1200 5250 RGB 0500 0960 N1 1000 960 976 893 1200 6002 RGB 0500 1080 N1 1300 1080 1269 ...
Страница 7: ...cal damage sustained during shipment If damaged file a claim with the shipper and return for repair following the procedures outlined on the back cover If no damage is observed remove all shipping restraints and padding Check AC REGEN nameplate data for conformance with the AC power source and motor DETERMINING CONTROL LOCATION The AC REGEN is suitable for most well ventilated factory areas where ...
Страница 8: ...on transformer is required are as follows 1 If the AC input power system does not have a neutral or one phase referenced to ground an isolation transformer with the neutral of the secondary grounded is highly recommended If the line to ground voltages on any phase can exceed 125 of the nominal line to line voltage an isolation transformer with the neutral of the secondary grounded is always requir...
Страница 9: ...point Grounding Sensitive Circuits It is critical to control the paths through which high frequency ground currents flow Sensitive circuits should not share a path with such currents Control and signal conductors should not be run near or parallel to power conductors Power Cabling Input and Output power connections are made through the power terminal block and power ground stud The actual AC REGEN...
Страница 10: ...rom the drive before drilling and punching holes to avoid metal dust inside the drive enclosure Failure to do so will cause damage to the drive For through panel mounting customer is to seal for gap on all side of cutout Provided by customer aluminum angle 1 x 1 x 0 050 can be used to attach to all sides of drive to help seal and secure the drive Figure 2 AC Regen Mounting Information Size 1 Nema ...
Страница 11: ...om the drive before drilling and punching holes to avoid metal dust inside the drive enclosure Failure to do so will cause damage to the drive For through panel mounting customer is to seal for gap on all side of cutout Provided by customer aluminum angle 1 x 1 x 0 050 can be used to attach to all sides of drive to help seal and secure the drive Figure 2 2a AC Regen Mounting Information Size 2 Nem...
Страница 12: ...es to avoid metal dust inside the drive enclosure Failure to do so will cause damage to the drive For through panel mounting customer is to seal for gap on all side of cutout Provided by customer aluminum angle 1 x 1 x 0 050 can be used to attach to all sides of drive to help seal and secure the drive Size 3 enclosure can also be free standing with optional floor stand kit from US Drives Inc Figur...
Страница 13: ...REGENERATIVE DC COMMON BUS SUPPLY 11 Figure 3 Size 1 2 3 Recommended Power Wiring ...
Страница 14: ...dc logic TB1 TERM 3 Regen Reset 24 Vdc logic TB1 TERM 4 Control circuit common TB2 TERM 1 2 Normally open contact energized when Regen is ON TB2 TERM 3 4 Normally open contact energized when Regen Precharge is complete Figure 4 Main Control Board Terminal Block Layout Table 5 Terminal Blocks Description for Control Board ...
Страница 15: ...rmal The first fault is automatically cleared after the control power supply stabilizes If a second fault occurs within a minute the fault is latched and clearing it requires a Regen reset LEDs at Start and Reset While the AC Regen is detecting the line frequency all LEDs except the Regen Active LED will be lit If the AC Regen reset line is held active the drive will rapidly flash every 100msec al...
Страница 16: ...lease note if an on board fuse soldered to the control board is open do not attempt to replace it An open on board fuse indicates a damaged board Visual Check Check all fuses boards wire harnesses connectors bus bars and enclosure walls for discoloration Ohmic Check Check IGBT personality boards for the following Burnt or discolored resistors R1 R2 R3 6 sets per Regen Shorted D1 D2 using meter set...
Страница 17: ...ated capacities whether intentional or unintentional d non authorized service repair modification transportation or installation Nor shall the manufacturer ever be liable for consequential or incidental damages including any lost profits or lost savings There are no other warranties expressed or implied which extend beyond that described herein The warranty set forth is exclusive and no other warr...
Страница 18: ... in U S A THE HIGH HORSEPOWER DESIGN EXPERTS US Drives Inc 2221 Niagara Falls Boulevard P O Box 281 Niagara Falls NY 14304 0281 Tel 716 731 1606 Fax 716 731 1524 Visit us at www usdrivesinc com Products Designed and Manufactured In The United States of America ...