If the end-of-charge voltage does not exceed the values above, check the charger
to ensure the proper output is being maintained. Recharge the batteries and mea-
sure again. If the pack voltage is still low, you may have a bad battery.
●
While the pack is on charge, measure the individual battery voltages and compare
to the table below. If the minimum voltage is not attained and/or the variance be-
tween the batteries is greater than the allowable variation, the low battery may be
failing.
TABLE 7
On-charge Test Threshold
Nominal Battery
Voltage
Minimum Voltage
Threshold
Allowable Variation within a
Set
6V
7V
0.5V
8V
9.3V
0.7V
12V
14V
1.0V
8.5 OPEN CIRCUIT VOLTAGE TESTING
This is the least preferred method of evaluating the condition of your battery due to the
misleading nature of open circuit voltages.
●
For accurate voltage readings, flooded lead acid batteries should remain idle
for at least 4-6 hours. AGMs should remain idle for at least 24 hours.
●
Measure the individual battery voltages.
●
If any recorded voltage differs from another battery within the set by more than
0.3V, you may have a failing battery.
8
TROUBLESHOOTING
Flooded Lead Acid Battery State of charge vs Specific Gravity
and Open Circuit Voltage
Depth of
Discharge
State of
Charge
(%)
Specific
Gravity
Corrected
to 80ºF
Open-Circuit Voltage
6V
8V
12V
24V
36V
48V 108V
0%
100
1.270
6.37
8.49
12.73
25.46 38.20 50.93 114.7
10%
90
1.246
6.31
8.41
12.62
25.24 37.85 50.47 113.6
20%
80
1.221
6.25
8.33
12.50
25.00 37.49 49.99 112.5
30%
70
1.197
6.19
8.25
12.37
24.74 37.12 49.49 111.4
40%
60
1.172
6.12
8.16
12.24
24.48 36.72 48.96 110.2
50%
50
1.148
6.05
8.07
12.10
24.20 36.31 48.41 108.9
60%
40
1.123
5.98
7.97
11.96
23.92 35.87 47.83 107.6
70%
30
1.099
5.91
7.88
11.81
23.63 35.44 47.26 106.4
80%
20
1.074
5.83
7.77
11.66
23.32 34.97 46.63 104.9
90%
10
1.050
5.75
7.67
11.51
23.02 34.52 46.03 103.5
100%
0
1.025
5.68
7.57
11.35
22.70 34.05
45.4 102.2
#Cells
3
4
6
12
18
24
54
AGM Battery State of Charge vs Open Circuit Voltage
Depth of
Discharge
State
of
Charge
(%)
AGM Battery Open-Circuit Voltage
6V
8V
12V
24V
32V
48V
108V
0%
100
6.50
8.67
13.00
26.00
39.00
52.00
117.0
10%
90
6.44
8.58
12.87
25.75
38.62
51.50
115.9
20%
80
6.37
8.50
12.75
25.50
38.24
50.99
114.7
30%
70
6.31
8.41
12.62
25.24
37.87
50.49
113.6
40%
60
6.25
8.33
12.50
24.99
37.49
49.98
112.5
50%
50
6.19
8.25
12.37
24.74
37.11
49.48
111.3
60%
40
6.12
8.16
12.24
24.49
36.73
48.98
110.2
70%
30
6.06
8.08
12.12
24.24
36.35
48.47
109.1
80%
20
6.00
7.99
11.99
23.98
35.98
47.97
107.9
90%
10
5.93
7.91
11.87
23.73
35.60
47.46
106.8
100%
0
5.87
7.83
11.74
23.48
35.22
46.96
105.7
#Cells
3
4
6
12
18
24
54
TABLE 8
TABLE 9
QUICK TIP
SINGLE POINT WATERING KITS:
ARE A
GREAT WAY TO REDUCE THE AMOUNT OF TIME IT
TAKES TO MAINTAIN YOUR FLOODED BATTERIES. ALL
BATTERIES CAN BE WATERED FROM ONE SOURCE.
THE VALVES ENSURE THAT ELECTROLYTE LEVELS ARE
PROPERLY MAINTAINED. FOR MORE INFORMATION
VISIT