Figure 60 - Diagrams of input connections
IMPORTANT!
In order to maintain conformity with Standard EN50131-3, the CUSTOMIZATION functions of the
INPUTS present in the control panel must be modified.
IMPORTANT!
In order to maintain conformity with Standard EN50131, the inputs must not be programmed as
NORMALLY CLOSED and NORMALLY OPEN in that they would not be protected against short circuits and cut
wires.
IMPORTANT!
In order to maintain conformity with Standard EN50131, the inputs must not be programmed as
SHOCK and ROLLER in that they would not be protected against short circuits.
IMPORTANT!
Each sensor must be powered by the device that controls it (control panel, expansion, keypad, or
reader). The balancing resistors must be connected to the positive of the power supply of the same device.
Connections with different power supplies may cause false alarms.
It due to wiring problems this is not possible use the NC or NO type inputs.
Colour code for 2.7 kohm, tolerance 1%
All the resistors provided with the 1067 system are 2.7 kohm, tolerance 1%.
IMPORTANT!
It is not necessary to close the unused inputs because they can be excluded via the programming.
IMPORTANT!
The SAB inputs must also be reclosed by a 2.7 kohm balancing resistor.