4.2 Installation Location
Make sure that the installation location meets the following conditions:
• The area is completely water proof.
• The floor is flat and level.
• There are no flammable or explosive materials.
• The ambient temperature is within the range from 0°C to 50°C.
• The temperature and humidity is maintained at a constant level.
• There is minimal dust and dirt in the area.
• The distance from heat source is more than 2 meters
• The distance from air outlet of inverter is more than 0.5 meters.
• The installation area shall avoid of direct sunlight.
• There is no mandatory ventilation requirements for battery module, but please avoid of installation in
confined area.The aeration shall avoid of high salinity, humidity or temperature.
CAUTION
If the ambient temperature is out of the operating range, the battery stops operating to protect itself. The
optimal temperature range for the battery pack to operate is 10°C to 40°C. Frequent exposure to harsh
temperatures may deteriorate the performance and life of the battery.
product manual
UE-48Li3600V2
4.3 Grounding
Grounding cables shall be 10 AWG or higher yellow-green cables. After connection, the resistance from
battery grounding point to Ground connection point of room or installed place shall smaller than 0.1Ω.
1) Based on metal directly touch between the module’s surface and rack’s surface.
If using painted rack the corresponding place shall remove the paintingtion in
confined area.The aeration shall avoid of high salinity, humidity or temperature.
2) Install a grounding cable to the grounding point of the modules.