6. ELECTRICAL DATA
6.1. Power Data of Basic Elements and Options
SERİ [BSC_SS]
URTP
055
URTP
070
URTP
090
URTP
110
URTP
140
URTP
180
URTP
230
EXPLANATION
Installed Power without Option [For Low Pressure]
W
17081
20550
27847
32390
40830
52780
69650
Current in Nominal Capacity **
A
26,1
30,5
39,9
40,5
50,3
64,5
83,4
Current in Maximum Capacity
A
32,5
39,1
52,9
61,6
77,6
100,4
132,4
Start up Current
A
121
136
172
177
219
260
279
Installed Power without Option [For Middle
Pressure]
W
17481
21250
28647
33190
42230
54380
71650
Current in Nominal Capacity**
A
27,1
32,0
41,5
42,6
52,0
67,7
87,4
Current in Maximum Capacity
A
32,3
40,4
54,5
63,1
80,3
103,4
136,2
Start up Current
A
122
138
174
179
222
264
283
Installed Power without Option [For High Pressure]
W
18181
22050
30047
34590
43830
56380
74650
Current in Nominal Capacity**
A
28,5
33,6
44,3
45,4
54,9
71,7
93,4
Current in Maximum Capacity
A
34,5
41,9
57,1
65,8
83,3
107,1
141,5
Start up Current
A
124
140
177
182
226
268
289
OPTIONS and ACCESSORIES
Power Consumed for Natural Gas Firing Unit
W
74
74
97
97
123
130
130
Natural Gas Firing Unit
A
0,33
0,33
0,44
0,44
0,56
0,59
0,59
Consumed Power of Return Fan Unit
W
540
770
860
1080
1540
2140
2000
Current Draw of Return Fan Unit
A
1,1
1,5
0,8x2
1,1x2
1,5x2
2,1x2
1,8x2
Consumed Power of Exhaust Fan Unit
W
190
260
380
380
520
660
860
Current Draw of Exhaust Fan Unit
A
0,4
0,5
0,4x2
0,4x2
0,5x2
1,4x2
0,8x2
Consumed Power of Electric Unit [High Cap./ Stage
1]
W
11500
15000
18000
22000
30000
40000
50000
Consumed Power of Electric Unit [High Cap./ Stage
1]
A
16,62
21,67
26
31,78
43,34
57,78
72,23
Consumed Power of Electric Unit [High Cap./ Stage
2]
W
22500
28000
37000
45000
55000
70000
90000
Consumed Power of Electric Unit [High Cap./ Stage
2]
A
32,50
40,45
53,45
65,0
79,45
101,12
130,0
Consumed Power of Electric Unit [Low Cap./ Stage
1]
W
6000
8000
10000
13000
16000
20000
26000
Consumed Power of Electric Unit [Low Cap./ Stage
1]
A
8,67
11,56
14,45
18,78
23,12
28,89
37,56
Consumed Power of Electric Unit [Low Cap./ Stage
2]
W
13000
16000
21000
25000
32000
41000
52000
Consumed Power of Electric Unit [Low Cap./ Stage
2]
A
18,78
23,12
30,34
36,12
46,24
59,24
75,14
* Users should add option or accessory power values, if available, to the installed power to find out about power
value of their own device.
** 400V is the power inlet in nominal voltage.
*** Standardized Eurovent Conditions: By wet thermometer, the inner ambient temperature is 19°C, in
standard fan performance; the external ambient temperature is 35°C.