Electric Combination Boiler User Manual
SELECTION OF INSTALLATION PLACE
Electric boilers do not require a chimney for installation, they can be
installed in electrically suitable places. The minimum dimensions to
be observed during installation are given in the figure below. If more
than one combi boiler is connected, the space in which the boiler is
installed must have sufficient free space for installation and
maintenance of the boiler. For service needs, the heater must be far
enough from the ceiling to be able to easily remove the heating elements. If a single boiler is used, it should be
at least 40 cm from the wall and at least 30 cm from the ceiling. For the installation of two side-by-side
combinations, the previous rule applies and in addition, the distance between the two coils must be at least 40
cm.
The base or wall where the boiler is to be placed must be flat and strong enough to carry the device. It should be
hung to a stable and stable wall so that it does not come into the brick cavities. It should be ensured that the
inlet and outlet pipes of the combi are connected as in the boiler connection diagram and there should be no
water leakage. The connection of the phase and neutral inputs must be entered into the fuse and neutral terminal
on the boiler as in the connection diagram. Phase and neutral inputs should be tightened too tightly and not
loose. Combi and electrical connections must be made to qualified craftsmen. Safety fuse must be left within 50
cm to the side of the boiler.
There should be no power line near the boiler, defective and suspicious for safety.
Leave enough space around the boiler for possible service intervention
SAFETY PRECAUTIONS
The electrical installation of this product must be carried out by authorized personnel in accordance
with the instructions given in this manual and the applicable local or national regulations.
THIS PRODUCT MUST BE EARTH!
THIS PRODUCT MUST BE CONNECTED TO THE ELECTRICITY WITH A LEAD CURRENT RELAY!
The boiler must be connected to the electrical installation in accordance with the specifications in the manual
and the relevant regulations.
The power source to which the boiler must be connected must be capable of feeding the boiler. To protect the
appliance, the device must be connected to the power supply line (see TABLE I below) in proportion to the current
of the device. The device must be connected to its own independent power line; the lighting should not be
connected to the buzzer or the furnace line.