background image

Unitronics  

Vision™ OPLC™

 

V350-35-R34 
Installation Guide

 

The Unitronics V350-35-R34 offers the following onboard I/Os: 

22 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder Inputs   
12 Relay Outputs 

General Description 

V350 OPLCs are micro-OPLCs, rugged programmable logic controllers that comprise:  

On-board I/O configuration 
Built-in operating panel containing a 3.5” Color Touchscreen and programmable function keys  

Communications 

1 built-in serial port: RS232/RS485  
Optional: the user may order and install 
one or both of the following modules:  
- RS232/RS485/Ethernet  
- CANbus  
Communication Function Blocks 
 include: SMS, GPRS, MODBUS 
serial/IP. Protocol FB enables PLC to 
communicate with almost any external 
device, via serial or Ethernet 
communications 

I/O Options 

V350 supports digital, high-speed, analog, 
weight and temperature measurement I/Os via: 

On-board I/O configuration
Model-dependent 
I/O Expansion Modules
Local or remote I/Os may be added via 
expansion port or CANbus.  

Information Mode 

This mode enables you to: 

View & Edit operand values, COM port settings, RTC and screen 
contrast/brightness settings 
Calibrate the touchscreen 
Stop, initialize, and reset the PLC 

To enter Information Mode, press the <i> button for several seconds. 

Programming 
Software,  
& Utilities 

The Unitronics Setup CD contains VisiLogic software and other utilities 

VisiLogic
Easily configure hardware and write both HMI and Ladder control 
applications; the Function Block library simplifies complex tasks 
such as PID. Write your application, and then download it to the 
controller via the programming cable included in the kit. 
Utilities
Includes UniOPC server, Remote Access for remote programming 
and diagnostics, and DataXport for run-time data logging. 

To learn how to use and program the controller, as well as use utilities such 
as Remote Access, refer to the VisiLogic Help system. 

 

Содержание Vision OPLC V350-35-R34

Страница 1: ...nd temperature measurement I Os via On board I O configuration Model dependent I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Calibrate the touchscreen Stop initialize and reset the PLC To enter Information Mode press the i button fo...

Страница 2: ...g this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry...

Страница 3: ...oller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure...

Страница 4: ... kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Inse...

Страница 5: ...t of a shaft encoder or as normal digital inputs If inputs 0 2 and 4 are set as high speed counters without reset inputs 1 3 and 5 can function as normal digital inputs Input Jumper Settings The tables below show how to set a specific jumper to change input functionality To access the I O jumpers you must open the controller according to the instructions beginning on page 9 Incompatible jumper set...

Страница 6: ...ics npn Input Wiring Input wiring npn sink HSC input wiring npn sink pnp Input Wiring Input wiring pnp source HSC input wiring pnp source Shaft encoder Analog Input Wiring Analog Input Wiring Current 2 Wire Analog Input Wiring Current 3 Wire ...

Страница 7: ...al is connected to the chassis Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supp...

Страница 8: ...RS485 remove the RS485 connector and connect the PC to the PLC via the programming cable Note that this is possible only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 ...

Страница 9: ...enabling you to change I O settings according to the jumpers shown on page 5 Changing Communication Settings 1 To access the communication jumpers hold the I O PCB board by its top and bottom connectors and steadily pull the board off 2 Locate the jumpers and then change the settings as required Jumper settings are shown on page 8 Closing the Controller 1 Gently replace the board Make certain that...

Страница 10: ...not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in the information presented in this document In no event shall Unitronics be liable for any special incidental indirect or consequential damages of any kind or any damages whatsoever arising out of or in connection with the use ...

Отзывы: