Connecting Expansion Modules 

An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to 
the adapter or to another module: 

1. 

Push the module-to-module connector into the port located on the right side of the device. 

Note that there is a protective cap provided with the adapter.  This cap covers the port of the 

final 

 I/O module in the system. 

To avoid damaging the system, do not connect or disconnect the device when the  
power is on. 

 

Component identification 

1

Module-to-module 
connector 

2

Protective cap 

1

2

Wiring 

 

Do not touch live wires. 

Unused pins should not be connected.  Ignoring this directive may damage the device. 

Double-check all wiring before turning on the power supply. 

Do not connect the ‘Neutral or ‘Line’ signal of the 110/220VAC to the device’s 0V pin. 

In the event of voltage fluctuations or non-conformity to voltage power supply specifications, 
connect the device to a regulated power supply. 

Double-check all the wiring before turning on the power supply. 

Wiring Procedures

Use crimp terminals for wiring; use 26-12AWG wire (0.13 mm 

2

–3.31 mm

2

) for all wiring purposes. 

1. 

Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  

2. 

Unscrew the terminal to its widest position before inserting a wire.  

3. 

Insert the wire completely into the terminal to ensure that a proper connection can be made. 

4. 

Tighten enough to keep the wire from pulling free.  

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 

Do not use tin, solder, or any other substance on stripped wire that might cause the wire strand to break. 

Install at maximum distance from high-voltage cables and power equipment. 

 

www.klinkmann.com

5 / 2011

Содержание EX-A2X

Страница 1: ...ions Only qualified service personnel should open this device or carry out repairs User safety and equipment protection guidelines This document is intended to aid trained and competent personnel in the installation of this equipment as defined by the European directives for machinery low voltage and EMC Only a technician or engineer trained in the local and national electrical standards should pe...

Страница 2: ...s Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Leave a minimum of 10mm space for ventilation between the top and bottom edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation M...

Страница 3: ...X A2X Use the communication cable to connect the module s PLC expansion port to the PLC Take care to connect the correct cable The connectors of this cable are housed in yellow insulation Note that one end is marked To PLC and the other To Adapter insert accordingly The module is supplied with a 1 meter cable part number EXL CAB100 Other cable lengths are also available Use only an original Unitro...

Страница 4: ...the power supply Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Double check all the wiring before turning on the power supply Wiring Procedures Use crimp terminals for wiring use 26 12AWG wire 0 13 mm 2 3 31 mm2 for all wi...

Страница 5: ...upply The EX A2X and the OPLC must be turned on and off simultaneously POWER 0V V EX A2X Technical Specifications I O module capacity Up to 8 I O modules can be connected to a single adapter Power supply 12VDC or 24VDC Permissible range 10 2 to 28 8VDC Max current consumption 650mA 12VDC 350mA 24VDC Typical power consumption 4W Current supply for I O modules 1A max from 5V see Note 1 Galvanic isol...

Страница 6: ... 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will be addressed as I 67 67 32 2 16 3 Output 4 located on expansion module 3 in the system will be addressed as O 84 84 32 3 16 4 EX90 DI8 RO8 is a stand alone I O module Even if it is the only module in the configuration the EX90 DI8 RO8 is always assigned the nu...

Отзывы: