Control connection
DS 400-2
04/2019 - V01
50
Erro
r d
isp
la
y o
n t
he
se
rv
o
5.13
Error display on the servo
The red LED "fault" is bright and the fault no. is indicated by the green seven-segment display.
List of faults/errors
Display
controller
Fault display on the
NDrive
Meaning
0
BADPARAS
Damaged parameter
1*
POWER FAULT
Output stage error
2
RFE FAULT
Safety bus fault
3
BUS TIMEOUT
Transmission fault BUS
4
FEEDBACK
Encoder signal faulty
5
POWERVOLTAGE
No power supply voltage
6
MOTORTEMP
Motor temperature too high
7*
DEVICETEMP
Device temperature too high
8
OVERVOLTAGE
Overvoltage >1.8 x UN
9
I_PEAK
Over-current 300 %
A
RACEAWAY
Drive races
(without command value, wrong direction)
B
USER
User - choice of error
C
12R
Overload
D
RESERVE
E
CPU-ERROR
Software error
F
(device-dependent)
BALLAST
Ballast circuit overloaded
Decimal point flashing
Processing unit active
Decimal point dark
Auxiliary voltage missing or inherent hardware failure
Fau
lt
Beispiel:
POWERVOLTAGE
(Power voltage missing)
FAULT LED rot
Fault no. 5
* DEVICETEMP
For the DS405, 412, 420 the IGBT over-temperature is signaled as fault 1 POWER FAULT (output
stage fault).
Note
: When applying the 24V auxiliary voltage with the enable closed (FRG/RUN X1:7 active) the
red LED signals an error. There is no fault signal displayed in the 7-segment display.