FSUIM Universal Interface 
Module Installation Sheet 

 

Description 

The FSUIM Universal Interface Module provides five common control 
switch inputs and nine common relay outputs. Typically, the FSUIM is 
used in a graphic annunciator connected to an F-series fire alarm 
control panel. 

LEDs provide visual indication when a relay is energized. 

The FSUIM is shipped with a plastic snap track for mounting in an 
MFC-A cabinet. 

Installation 

Install the FSUIM according to the instructions provided below. The 
FSUIM will not operate properly until detected by the control panel. 

You can only install one FSUIM per system. 

For more information, refer to the technical reference manual listed 
inside the control panel door. 

Caution: 

Make sure all power is disconnected from the panel before 

installing. Observe static-sensitive handling practices. 

To install the FSUIM: 

1.  Mount the snap track in the MFC-A cabinet as shown in Figure 1. 

You can also mount the snap track vertically, if required. 

2.  Insert the bottom edge of the FSUIM into the snap track then press 

the top edge in until it snaps into place. 

3.  Wire the FSUIM as shown in Figure 1. Verify that all wiring is free 

of opens, shorts, and ground faults. 

Legend for Figure 1 

(1)  All wiring is supervised and power-limited unless noted otherwise. 

(2)  Only the trouble relay and power relay are energized when power 

is applied. 

(3)  AUX power supplied by the control panel can’t exceed 0.5 A. If 

more than 0.5 A is required, you must use a power-limited and 
regulated 24 VDC auxiliary/booster power supply that is UL/ULC 
Listed for fire protective signaling systems. 

(4)  If powered from an external supply, the supply must be installed 

in the same room as the control panel and their 24 VDC 
commons (−) wired together. 

(5)  Relay outputs are not supervised and do not provide current 

limiting. Connect relays only to power-limited sources. 

(6)  Use momentary switches only. 

(7)  Mount LEDs and switches in separate cabinet located in the same 

room as the FSUIM. 

Specifications 

 

Voltage 

21.2 to 27.3 VDC 

Current  
 

Standby 

 

Alarm 

 
53 mA 
114 mA 

Circuit capacitance 

0.03 μF, max. 

Circuit resistance 

13 Ω, max. 

Ground fault impedance 

0 Ω 

Switch inputs 
 

Quantity 

 

Wiring Class 

 

End-of-line resistor 

 

Class B 

4.7 kΩ 1/2 W 

Relay outputs 
 

Quantity 

 

Type 

 

Style 

 

Contact rating 

 

Wiring Class 

 

Common 
Form C 
30 Vdc at 1 A (resistive load) 
Class E 

Wire size 

12 to 18 AWG (0.75 to 2.5 mm²) 

Mounting 

MFC-A cabinet 

Operating environment 
 

Temperature 

 

Relative humidity 

 
0 to 49 °C (32 to 120 °F) 
0 to 93% noncondensing 

 

Contact information 

For contact information, see www.edwardsfiresafety.com. 