39
Table 6 — Menu Structure
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
NOTES
STATUS
ECONO AVAIL
NO
YES/NO
FIRST STAGE COOLING DEMAND (Y1–IN)
YES = economizing available; the system can use outside air for free
cooling when required
ECONOMIZING
NO
YES/NO
FIRST STAGE COOLING RELAY OUTPUT
YES = outside air being used for 1 stage cooling
OCCUPIED
NO
YES/NO
OCCUPIED
YES = OCC signal received from space thermostat or
unitary controller
YES = 24 Vac on terminal OCC
NO = 0 Vac on terminal OCC
HEAT PUMP
N/A
COOL
HEAT
HEAT PUMP MODE
Displays COOL or HEAT when system is set to heat pump
(Non-conventional)
COOL Y1—IN
OFF
ON/OFF
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1–I signal from space thermostat or unitary controller for cooling stage
1.
ON = 24 Vac on terminal Y1–I
OFF = 0 Vac on terminal Y1–I
COOL Y1—OUT
OFF
ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
Cool stage 1 Relay Output to stage 1 mechanical cooling
(Y1–OUT terminal)
COOL Y2—IN
OFF
ON/OFF
SECOND STAGE COOLING DEMAND (Y2–IN)
Y2–I signal from space thermostat or unitary controller for second stage
cooling.
ON = 24 Vac on terminal Y2–I
OFF = 0 Vac on terminal Y2–I
COOL Y2—OUT
OFF
ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
Cool Stage 2 Relay Output to mechanical cooling
(Y2–OUT terminal)
MA TEMP
_ _ . _ F
0 to 140 F
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from MAT sensor.
Displays _ _ . _ F if not connected, short or out-of-range.
DA TEMP
_ _ . _ F
0 to 140 F
DISCHARGE AIR TEMPERATURE, after Heating section
Displays when Discharge Air sensor is connected and displays mea-
sured discharge temperature.
Displays _ _ . _F if sensor sends invalid value, if not connected, short or
out-of-range.
OA TEMP
_ _ . _ F
-40 to 140 F
OUTSIDE AIR TEMP
Displays measured value of outdoor air temperature.
Displays _ _ . _F if sensor sends invalid value, short or
out-of-range.
OA HUM
_ _ %
0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from
OA sensor.
Displays _ _% if not connected short, or out-of-range.
RA TEMP
_ _ . _ F
0 to 140 F
RETURN AIR TEMPERATURE
Displays measured value of return air temperature from
RAT sensor.
Displays _ _ . _ F if sensor sends invalid value, if not connected, short or
out-of-range
RA HUM
_ _ %
0 to 100%
RETURN AIR RELATIVE HUMIDITY
Displays measured value of return air humidity from
RA sensor.
Displays _ _% if sensor sends invalid value, if not connected, short or
out-of-range
IN CO2
_ _ _ ppm
0 TO 2000 ppm
SPACE/RETURN AIR CO
2
Displays value of measured CO
2
from CO
2
sensor. Invalid if not con-
nected, short or out-of-range
DCV STATUS
N/A
ON/OFF
DEMAND CONTROLLED VENTILATION STATUS
Displays ON if above setpoint and OFF if below setpoint, and ONLY if a
CO
2
sensor is connected.
DAMPER OUT
2.0v
2.0 TO 10.0v
Displays voltage output to the damper actuator.
ACT POS
N/A
0 to 100%
Displays actual position of outdoor air damper actuator
Содержание Carrier WeatherMaker 50TC A08 Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Size 08 09 12 Units...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 08 09 12 Units cont...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 Unit...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 Unit cont...
Страница 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 Unit cont...
Страница 13: ...13 Fig 8 Roof Curb Details Size 16 Unit...
Страница 33: ...33 Fig 62 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring 50TC 08 14 Unit Sizes...
Страница 34: ...34 Fig 63 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring 50TC 16 Unit Sizes HUMIDISTAT...
Страница 50: ...50 Fig 73 50TC 16 Control Box Component PremierLink Locations...
Страница 51: ...51 Fig 74 Typical PremierLink Control Wiring Diagram...
Страница 52: ...52 Fig 75 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option...
Страница 64: ...64 Fig 106 Typical RTU Open Controller Wiring Diagram 50TC 08 14 Size Units...
Страница 65: ...65 Fig 107 Typical RTU Open Controller Wiring Diagram 50TC 16 Size Unit...
Страница 66: ...66 Fig 108 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option 50TC 08 14 Size Units...
Страница 67: ...67 Fig 109 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option 50TC 16 Size Units...