22
2. Install jumpers between R-W2 and W2-W1 on TB4 in
the control box.
3. Under the
Setpoints
menu, the following configurations
should be set:
4. The degrees of demand from the space temperature set-
points are configured under the
Configuration
D.LV.T
submenu. See the Heating Control and Cooling Control
sections for further description on these configurations.
Configure the following setpoints:
5. Under
Configuration
UNIT
SENS
SPT.S
, enable
the space sensor by setting
SPT.S
to ENBL.
6. Under
Configuration
UNIT
CV.FN
, set
CV.FN
to 1
for continuous fan or 0 for automatic fan.
7. To program time schedules, set
SCH.N
=1 under
Config-
uration
CCN
SC.OV
SCH.N
to configure the
control to use local schedules.
8. Under the
Timeclock
SCH.L
submenu, enter the de-
sired schedule. See Time Clock Configuration section on
page 77 for further description of these configurations.
9. See the Economizer Options section below for additional
economizer option configurations.
10. See the Exhaust Options section on this page for
additional exhaust option configurations.
Economizer Options —
Under the
Configuration
ECON
submenu, the following setpoints may be configured:
Configuration
ECON
EC.MN
should always be set for
the minimum damper position. While practicing dual setpoint
usage,
Cofiguration
ECON
EP.MS
and
EP.XS
are needed
to set up the dual minimum damper positions. The controller
would enforce
EP.MS
EP.XS
.
Indoor Air Quality (IAQ) Options
DEMAND CONTROLLED VENTILATION — Under
Configuration
IAQ
DCV.C
, the following configuration
parameters should be set to establish the minimum and maxi-
mum points for outdoor air damper position during demand
controlled ventilation (DCV):
EC.MN
Economizer Min. Position
EP.MS
Economizer Position at Min. VFD
EP.XS
Economizer Position at Max. VFD
IAQ.M
IAQ Demand Vent Min. Pos.
Configuration
IAQ
DCV.C
IAQ.M
is used to set the
absolute minimum vent position (or maximum reset) under
DCV.
Configuration
IAQ
EP.MS
and
EP.XS
are needed to
setup the dual minimum damper positions.
Configuration
IAQ
DCV.C
EC.MN
is used to set the
minimum damper position (or with no DCV reset). This is also
referenced in the economizer section.
Exhaust Options —
The A Series units can be config-
ured with constant volume 2-stage power exhaust or modulat-
ing power exhaust. The following exhaust options should be
configured.
Configuration
BP
BF.CF
=1
(Two-Stage Exhaust Option)
— For two-stage exhaust, under the
Configuration
BP
sub-
menu, configure the following:
Configuration
BP
BF.CF
=2
(Modulating Power Exhaust
Option) — For modulating exhaust, in the
Configuration
BP
submenu, configure the following:
Programming Operating Schedules —
The
Comfort
Link controls will accommodate up to eight dif-
ferent schedules (Periods 1 through 8), and each schedule is
assigned to the desired days of the week. Each schedule
includes an occupied on and off time. As an example, to set an
occupied schedule for 8 AM to 5 PM for Monday through Fri-
day, the user would set days Monday through Friday to ON for
Period 1. Then the user would configure the Period 1 Occupied
From point to 08:00 and the Period 1 Occupied To point to
17:00. To create a different weekend schedule, the user would
use Period 2 and set days Saturday and Sunday to ON with the
desired Occupied On and Off times. To create a schedule, per-
form the following procedure:
NOTE: By default, the time schedule periods are programmed
for 24 hours of occupied operation.
1. Scroll to the Configuration mode, and select CCN
CONFIGURATION (
CCN
). Scroll down to the Schedule
Number (
Configuration
CCN
SC.OV
SCH.N
). If
password protection has been enabled, the user will be
prompted to enter the password before any new data is
accepted.
SCH.N
has a range of 0 to 99. The default val-
ue is 1. A value of 0 is always occupied, and the unit will
control to its occupied setpoints. A value of 1 means the
unit will follow a local schedule, and a value of 65 to 99
means it will follow a CCN schedule. Schedules 2 to 64
are not used as the control only supports one internal/
local schedule. If one of the 2 to 64 schedules is config-
ured, then the control will force the number back to 1.
Make sure the value is set to 1 to use a local schedule.
2. Enter the Time Clock mode. Scroll down to the LOCAL
TIME SCHEDULE (
SCH.L
) sub-mode, and press
ENTER. Period 1 (
PER.1
) will be displayed. Press
ENTER to configure Period 1.
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
SA.HI
Supply Air Setpoint Hi
SA.LO
Supply Air Setpoint Lo
L.H.ON
Demand Level Lo Heat On
H.H.ON
Demand Level Hi Heat On
L.H.OF
Demand Level Lo Heat On
L.C.ON
Demand Level Lo Cool On
H.C.ON
Demand Level Hi Cool On
L.C.OF
Demand Level Lo Cool On
EC.EN
Economizer Enabled?
EC.MN
Economizer Min.Position
EC.MX
Economizer Maximum Position
EP.MS
Economizer Position at Min. VFD
EP.XS
Economizer Position at Max. VFD
E.TRM
Economizer Trim for SumZ?
E.SEL
Econ Changeover Select
OA.E.C
OA Enthalpy Change Over Select
OA.EN
Outdoor Enthalpy Compare Value
OAT.L
High OAT Lockout Temp
O.DEW
OA Dew Point Temp Limit
ORH.S
Outside Air RH Sensor
BP.P1
Power Exhaust On Setp. 1
BP.P2
Power Exhaust On Setp. 2
BP.SP
Building Pressure Setp.
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...