17
2
6.3 - Minimum chilled water flow
The minimum chilled water flow is shown in the table in
chapter 6.7 “Evaporator and condenser water flow rates”.
If the system flow is less than the minimum unit flow rate,
the evaporator flow can be recirculated, as shown in the
diagram.
For minimum chilled water flow rate
Legend
1. Evaporator
2. Recirculation
6.4 - Maximum chilled water flow
The maximum chilled water flow is limited by the permitted
pressure drop in the evaporator. It is provided in the table in
chapter 6.7 “Evaporator and condenser water flow rates”.
•
Select the option with one water pass less that will
allow a higher maximum water flow rate (see option
100C in the table in chapter 6.6 “Number of passes”.
•
Bypass the evaporator as shown in the diagram to
obtain a lower evaporator flow rate.
For maximum chilled water flow rate
Legend
1. Evaporator
2. Bypass
6.5 - Condenser water flow rate
The minimum and maximum condenser water flow rates
are shown in the table in chapter 6.7 “Evaporator and
condenser water flow rates”.
If the system flow is higher than the maximum unit flow
rate, select the option with one pass less that will allow a
higher maximum water flow rate. Please refer to option
102C in the table in chapter 6.6 “Number of passes”.
6.6 - Number of passes
30XW-V/30XWHV
580
630
810
880
1150
1280
1470
1570
1710
Evaporator
Standard
2
2
2
2
2
2
2
2
2
Option 100C
1
1
1
1
1
1
1
1
1
Condenser
Standard
2
2
2
2
2
2
2
2
2
Option 102C
1
1
1
1
1
1
1
1
1
6.7 - Evaporator and condenser water flow rates
These below values are given for standard units. For options 100C and 102C, please refer to the unit selection program.
30XW-V/30XWHV
580
630
810
880
1150
1280
1470
1570
1710
Evaporator water flow rate, l/s
Minimum
10
10
13
13
25
25
25
25
25
Maximum
54
54
76
76
170
170
170
170
170
Condenser water flow rate, l/s
Minimum
6
6
8
8
15
15
15
15
15
Maximum
52
52
74
74
170
170
170
170
170
Notes
- Minimum evaporator flow rate based on a water velocity of 0,5 m/s.
- Minimum condenser flow rate based on a water velocity of 0,3 m/s.
2
1
1
2