5.3 - Power connection/disconnect switch

30XW-V/30XWHV 580-880 

units have one connection point

30XW-V/30XWHV 1150-1710: 
• 

Standard unit: two connection points

• 

Unit with option 81: one connection point.

5.4 - Recommended wire sections

Wire sizing is the responsibility of the installer, and depends 

on the characteristics and regulations applicable to each 
installation site. The following is only to be used as a 

guide-line, and does not make in any way liable. After wire 
sizing has been completed, using the certified dimensional 
drawing, the installer must ensure easy connection and 
define any modifications necessary on site. The connections 
provided as standard for the field-supplied power entry 

cables to the general disconnect/isolator switch are 

designed for the number and type of wires, listed in the 

second column of the table below.

The calculations for favourable and unfavourable cases are 
based on the maximum current for each unit (see electrical 
data tables). For the design the standardised installation 

methods in accordance with IEC 60364 are used: multicon-
ductor PVC (70°C) or XLPE (90°C) insulated cables with 

copper core; arrangement to comply with table 52c of the 
above standard. The maximum temperature is 42°C. The given 
maximum length is calculated to limit the voltage drop to 5%.

5.5 - Power cable entry

The power cables can enter the control box from above 
the unit. A removable aluminium plate on the upper part 
of the control box face allows introduction of the cables. 

Refer to the certified dimensional drawing for the unit.

5 - ELECTRICAL CONNECTION

Please refer to the certified dimensional drawings, supplied 

with the unit.

5.1 - Power supply

The power supply must conform to the specification on the 

unit nameplate. The supply voltage must be within the range 

specified in the electrical data table. For connection details 

refer to the wiring diagrams.

WARNING: Operation of the unit with an improper supply 
voltage or excessive phase imbalance constitutes abuse 
which will invalidate the Carrier warranty. If the phase 
imbalance exceeds 2% for voltage, or 10% for current, 

contact your local electricity supplier at once and ensure 
that the unit is not switched on until corrective measures 

have been taken.

5.2 - Voltage phase imbalance (%)

100 x max. deviation from average voltage

Average voltage

Example:

On a 400 V - 3 ph - 50 Hz supply, the individual phase 
voltages were measured to be:

AB = 406 V; BC = 399 V; AC = 394 V

Average voltage = (406 + 399 + 394)/3 = 1199/3
 

 

= 399.7 say 400 V

Calculate the maximum deviation from the 400 V average:

(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6

The maximum deviation from the average is 6 V. The 

greatest percentage deviation is: 100 x 6/400 = 1.5 %

This is less than the permissible 2% and is therefore 
acceptable.

Minimum and maximum connectable wire sections

Max. connectable 

wire section*

Calculation favourable case: Perforated horizontal conduit 

(standardised routing No. 13) - XLPE insulated cable

Calculation unfavourable case: Closed conduit (standard-

ised routing No. 41) - PVC insulated cable, if possible

30XW-V/30XWHV

Circuit(s) A/B

Section, mm² 

(per phase)

Section**, mm² 

(per phase)

Max. length, m

Cable type

Section**, mm² 

(per phase)

Max. length, m

Cable type***

Units without option

580

2 x 240

1 x 120

250

XLPE

1 x 240

420

PVC

630

2 x 240

1 x 150

250

XLPE

2 x 150

450

PVC

810

2 x 240

1 x 185

250

XLPE

2 x 185

450

PVC

880

2 x 240

1 x 240

280

XLPE

2 x 240

480

PVC

1150

2 x 240/2 x 240

1 x 120/1 x 120

250/250

XLPE

2 x 150/2 x 150 520

PVC

1280

2 x 240/2 x 240

1 x 150/1 x 150

250/250

XLPE

2 x 185/2 x 185 510

PVC

1470

2 x 240/2 x 240

1 x 240/1 x 150

310/250

XLPE

2 x 240/2 x 185 520/510

PVC

1570

2 x 240/2 x 240

1 x 240/1 x 240

310/310

XLPE

2 x 240/2 x 240 530/530

PVC

1710

2 x 240/2 x 240

1 x 240/1 x 240

280/280

XLPE

2 x 185/2 x 185 400/400

XLPE

Units with option 81

1150 to 1710

4 x 240

2 x 240

280

XLPE

 4 x 185

 320

XLPE 

*  Connection capacities actually available for each machine, defined according to the connection terminal size, the control box access opening size and the available 

space inside the control box.

**  Selection simultation result considering the hypothesis indicated.

***  If the maximum calculated section is for an XLPE cable type, this means that a selection based on a PVC cable type can exceed the connection capacity actually 

available. Special attention must be given to the selection.

Note:

 The currents considered are given for a machine equipped with a hydronic kit operating at maximum current.

Содержание Carrier Touchpilot 30XW-V

Страница 1: ...MAINTENANCE INSTRUCTIONS Variable Speed Water Cooled Liquid Chillers Variable Speed Water to Water Heat Pumps 30XW V 30XWHV Nominal cooling capacity 587 1741 kW Nominal heating capacity 648 1932 kW 5...

Страница 2: ...wiring 16 5 7 24 and 230 V power reserve for the user 16 6 APPLICATION DATA 16 6 1 Operating limits 16 6 2 Condenser side installation recommendation 16 6 3 Minimum chilled water flow 17 6 4 Maximum c...

Страница 3: ...lve 22 9 6 Pressure vessels 22 9 7 High pressure safety switch 23 9 8 Electronic expansion valve EXV 23 9 9 Moisture indicator 23 9 10 Filter drier 23 9 11 Sensors 23 9 12 Frequency variator 23 10 OPT...

Страница 4: ...the right place and direction on the unit The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings or lifting beams with the correct capacity an...

Страница 5: ...and may cause heart irregularities unconsciousness or death Vapour is heavier than air and reduces the amount of oxygen available for breathing These products cause eye and skin irritation Decomposit...

Страница 6: ...witch it is necessary to recover the refrigerant charge these pressure switches are not installed on automatic valves Schraeder type If any maintenance operations are carried out on the unit lock the...

Страница 7: ...These regulations permitting condi tioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people property and the environ...

Страница 8: ...t to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not inst...

Страница 9: ...on an even surface maximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components the number of support points is adequate and that...

Страница 10: ...ng an installation consult the certified dimensional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordina...

Страница 11: ...re of gravity coordinates refer to the dimensional drawings Condenser Evaporator Dimensions in mm A B C D E F 30XW V 30XWHV 1150 1997 1514 1164 4730 219 1 219 1 1280 1997 1514 1164 4730 219 1 219 1 14...

Страница 12: ...tonnes 186 186 257 250 172 172 172 164 157 Capacity control Touch Pilot inverter driven compressor electronic expansion valve EXV Minimum capacity 20 20 20 20 10 10 10 10 10 Evaporator Multi pipe floo...

Страница 13: ...380 421 Circuit B A 270 330 330 380 421 With option 81 A 540 660 710 760 842 Maximum power input with option 150B Circuit A kW 141 173 199 221 141 173 199 199 221 Circuit B kW 141 173 173 199 221 Wit...

Страница 14: ...with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power interruption in accordance with EN 60947 3 corresponds to IEC 60947 3 6 The units are d...

Страница 15: ...l electricity supplier at once and ensure that the unit is not switched on until corrective measures have been taken 5 2 Voltage phase imbalance 100 x max deviation from average voltage Average voltag...

Страница 16: ...ort Evaporator pump control signal Condenser pump control signal This does not control condenser pump operation for this function add option 156 and flow switch Heating cooling change over Available a...

Страница 17: ...ondenser water flow rates are shown in the table in chapter 6 7 Evaporator and condenser water flow rates If the system flow is higher than the maximum unit flow rate select the option with one pass l...

Страница 18: ...ecessary to add a buffer water tank to the circuit in order to achieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refe...

Страница 19: ...fewest elbows and horizontal pipe runs at different levels Below the main points to be checked for the connection Follow the water inlet and outlet connection direction shown on the unit Install manu...

Страница 20: ...es destabilisation of copper hydroxides and enlargement of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 pH 8 7 2 Water connections The water connections are Victau...

Страница 21: ...slave units Water inlet Water outlet Water pumps for each unit included as standard for units with hydronic module Additional sensors for leaving water control to be connected to channel 1 of the slav...

Страница 22: ...signed for prolonged storage of 15 years under nitrogen charge with a temperature difference of 20 K per day 452000 cycles start ups with a maximum difference of 6 K between two neighbouring points in...

Страница 23: ...re switches with manual reset called PZH former DBK are backed up by high pressure switches that require resetting with a tool The high pressure switches that require resetting with a tool are called...

Страница 24: ...s the unit by communication bus to a building management system 580 1710 LON gateway 148D Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to...

Страница 25: ...of the connections at the compressor terminals requires special precautions Please refer to the chapter below 11 STANDARD MAINTENANCE Air conditioning equipment must be maintained by profes sional tec...

Страница 26: ...is included with the compressor This low pressure switch should be temporarily installed as a hard safety on the high pressure part of the compressor The purpose of this switch is to protect the compr...

Страница 27: ...e the fan if a replace fan alert warning is displayed in the alarm list For any other alarm or problem at the frequency variator contact the Carrier service department The frequency variators in the 3...

Страница 28: ...properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is...

Страница 29: ...nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protec...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...es order No 13474 76 05 2013 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union www eurovent cer...

Отзывы: