
Installation
Wiring diagram for #33ZCT55CO2:
Wiring a Relative Humidity sensor
Part #33ZCSENSRH-02
The Relative Humidity (RH) sensor is used for zone humidity control (dehumidification) if the rooftop unit has a
dehumidification device. If not, the sensor only monitors humidity.
NOTE
Do not use a relative humidity sensor and CO
2
sensor on the same zone controller.
Wiring specifications
Cable from sensor to controller:
If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length:
500 feet (152 meters)
VAV Zone Controllers
21