Installation and Maintenance 

Instructions

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

IMT105-10

For remote mounting, fully immerse the bulb and 6” of capillary in the control 

zone. It is generally desirable to place the bulb close to the heating or cooling 

source in order to sense temperature fluctuations quickly. Be sure to locate 

the bulb so that it will not be exposed to temperatures beyond the instrument 

range limits.

WIRING

DIsconnecT  all  supply  cIrcuITs  BeFore  wIrIng  unIT.  

elecTrIcal raTIngs sTaTeD In lITeraTure anD on naMeplaTe 

MusT  noT  Be  eXceeDeD.    oVerloaD  on  a  swITcH  can  cause 

FaIlure  on  THe  FIrsT  cycle.    wIre  unITs  accorDIng  To 

naTIonal anD local elecTrIcal coDes.  MaXIMuM recoMMenDeD wIre 

sIZe Is 14 awg.

For proper TerMInal connecTIons, a FlaTHeaD screwDrIVer 

wITH  a  0.16”  wIDe  BlaDe  MusT  Be  useD  To  aVoID  DaMagIng 

TerMInal Block.

remove the two screws retaining the cover and cover gasket.  a 1/2” npT 

conduit  connection  is  located  on  the  left  side  of  the  enclosure.    connect 

conduit to the enclosure and wire directly to terminals according to local and 
national electrical codes.  a green grounding screw is provided.

Part II - Adjustments

Tools Needed

 phillips head and Flathead screwdriver

5/64” allen wrench

For  seT  poInT  aDjusTMenTs  anD  recalIBraTIon,  connecT 

conTrol To a calIBraTeD TeMperaTure source anD sTaBIlIZe 

unIT. 

remove adjustment cover on top of unit. Temperature setting is achieved by 

turning the knob and pointer against a reference scale.

re-InsTall  aDjusTMenT  coVer  aFTer  coMpleTIng  aDjusT-

MenTs.

controls are factory calibrated for maximum accuracy at the midpoint of the 

scale.

To recalibrate, turn knob and pointer to desired set point.  If the actual tem-

perature and set point temperature do not agree,  loosen 5/64”  allen set 

screws on adjustment knob and align pointer to indicate actual temperature.  

retighten allen set screws, and adjust knob and pointer to set point if neces-

sary.

GENERAL

Type B105 (Immersion Stem)

Temperature  variations  are  sensed  by  a  liquid  filled  sensor  which  expands 

or contracts against a bellows which in turn actuates or deactuates a snap-

action switch at a predetermined set point.

Type E105 (Bulb & Capillary)

Temperature variations of a liquid filled sensing bulb are hydraulically trans-

mitted to a bellows which either actuates or deactuates a snap-acting switch 
at a predetermined set point.

MaXIMuM  TeMperaTure  Is  THe  HIgHesT  TeMperaTure  To 

wHIcH  a  sensIng  eleMenT  May  Be  occasIonally  eXposeD 

To  wITHouT  aDVersely  aFFecTIng  seT  poInT  calIBraTIon 

anD  repeaTaBIlITy.  MaXIMuM  TeMperaTure  lIMITs  sTaTeD  In 

lITeraTure  anD  on  naMeplaTe  MusT  neVer  Be  eXceeDeD,  eVen  By 

TeMperaTure  oVersHooTs  In  THe  sysTeM.  occasIonal  operaTIon  oF 

unIT up To MaX. TeMperaTure Is accepTaBle (e.g., sTarT-up, TesTIng). 

conTInuous  operaTIon  sHoulD  Be  resTrIcTeD  To  THe  DesIgnaTeD 

aDjusTaBle range.

THIs proDucT Does noT HaVe FIelD replaceaBle parTs.

Part I - Installation

Tools Needed

screwdriver

adjustable wrench

MouNTING 

InsTall unIT wHere sHock,  VIBraTIon  anD TeMperaTure   F

lucTuaTIons are MInIMal.    Do  noT MounT unIT In  aMBIenT 

TeMperaTures  eXceeDIng  puBlIsHeD  lIMITs.    105  serIes 

TeMperaTure  swITcHes  can  Be  MounTeD  In  any  posITIon, 

proVIDeD THe elecTrIcal conDuIT Is noT FacIng up.  orIenT unIT so 

THaT MoIsTure Is preVenTeD FroM enTerIng THe enclosure.  

105 series remote and local mounted temperature controls can be surface 

mounted in any position via two 1/4” screw clearance holes on  the  enclo-
sure.  units  can  also  be  stem  mounted  using  pipe  thread  connection.  (see 

Dimensional drawings). 

For  local  MounTIng,  always  HolD  a  wrencH  on  THe  TeM-

peraTure HousIng HeX wHen MounTIng unIT. Do noT TIgHTen 

By TurnIng enclosure. THIs wIll DaMage sensor anD weaken 

solDereD or welDeD joInTs. 